Error Log Functions

 

 

Section 9-2

 

 

 

 

 

 

Error

Error

 

Detail code

Record

code

 

 

 

 

stored in

 

First byte

 

Second byte

(Hex)

 

 

EEPROM

 

 

 

 

0101

Transmission failed because the local node is

FINS message communications command:

No

 

not participating in the network.

Bit 15: OFF

 

 

 

 

 

Bits 14 to 8: SNA

 

 

 

0105

Transmission failed because of a node address

 

 

 

Bits 7 to 0: SA1

 

 

 

 

setting error.

 

 

 

 

FINS message communications response:

 

 

 

 

0106

Transmission failed because of a node address

 

Bit 15: ON

 

 

 

 

duplication error.

 

 

 

 

Bits 14 to 8: DNA

 

 

 

 

 

 

 

 

0107

Transmission failed because the other node is

 

 

 

Bits 7 to 0: DA1

 

 

 

 

not participating in the network.

 

 

 

 

Explicit message communications command:

 

 

 

 

0108

Transmission failed because there is no Unit

 

Bit 15: OFF

 

 

 

 

with the specified unit number.

Bits 14 to 8: 0

 

 

 

0109

Transmission failed because the other node is

Bit 7: ON

 

 

 

 

busy.

Bits 6 to 0: Node address of command source

 

 

 

Explicit message communications response:

 

010B

Transmission failed because of a CPU Unit

 

 

error. Frame discarded due to one of the follow-

Bit 15: ON

 

 

 

 

ing:

Bits 14 to 8: 0

 

 

 

 

• A cyclic service monitoring timeout occurred.

Bit 7: ON

 

 

 

 

Bits 6 to 0: Node address of command source

 

 

• A CPU Unit watchdog timer error occurred.

 

 

 

 

 

 

 

• Another CPU Unit error occurred.

 

 

 

 

 

 

 

 

 

 

010D

Transmission failed because the destination

 

 

 

 

 

address is not registered in the routing table.

 

 

 

 

 

 

 

 

 

 

010E

Transmission failed because the routing table

 

 

 

 

 

has not been registered.

 

 

 

 

 

 

 

 

 

 

010F

Transmission failed because of a routing table

 

 

 

 

 

error.

 

 

 

 

 

 

 

 

 

 

0110

Transmission failed because of too many repeti-

 

 

 

 

 

tions.

 

 

 

 

 

 

 

 

 

 

0111

Transmission failed because the command

 

 

 

 

 

exceeded the max. command length.

 

 

 

 

 

 

 

 

 

 

0112

Transmission failed because of a header error.

 

 

 

 

 

 

 

 

 

 

0117

Packet discarded because the internal recep-

 

 

 

 

 

tion buffer is full.

 

 

 

 

 

 

 

 

 

 

0118

Illegal packet discarded.

 

 

 

 

 

 

 

 

 

 

0120

Unexpected routing error

 

 

 

 

 

 

 

 

 

 

0123

Packet discarded because the internal trans-

 

 

 

 

 

mission buffer is full.

 

 

 

 

 

 

 

 

 

 

0124

Routing failed because maximum frame length

 

 

 

 

 

was exceeded.

 

 

 

 

 

 

 

 

 

 

0125

Packet discarded because of response timeout.

 

 

 

 

 

 

 

 

 

 

021A

Setting table logic error

00 Hex

 

03 Hex: Routing table

Yes

 

 

 

 

0A Hex: Master scan list

 

 

 

 

 

0B Hex: Slave scan list

 

 

 

 

 

0C Hex: Message moni-

 

 

 

 

 

toring timer list

 

 

 

 

 

 

 

0211

Node address duplication (cause)

00 Hex

 

Local node address

No

 

 

 

 

 

0300

Packet discarded because of parameter error.

Same as the code (such as 0101 Hex) in the dis-

No

 

 

carded FINS/explicit message packet.

 

 

 

 

 

 

 

0340

Bus Off detected

00 Hex

 

00 Hex

No

 

 

 

 

 

 

0341

Network power supply error

00 Hex

 

00 Hex

No

 

 

 

 

 

 

0342

Transmission timeout

00 Hex

 

00 Hex

No