Wired Remote I/O Systems | Section |
4-4 Wired Remote I/O Systems
Wired Remote I/O Master Units, Remote I/O Slave Units, and Remote Terminals can be directly connected with
Link Adapter
Link Adapter
Optical fiber (APF/PCF)
Master, Slave, or Remote Terminal
Master, Slave, or Remote Terminal
The Link Adapters must always be used in pairs, as they convert between wire and optical signals, thereby allowing optical transmission between Units which cannot themselves be connected directly to optical fiber cable. The entire Sub- system, from Master to terminator, must be connected in series, with no branch- ing. Up to 8 Link Adapters (4 pairs) can be used for each Master. The following diagram illustrates an acceptable configuration for a Wired Remote Master Sub- system, using the maximum of 8 Link Adapters for one Master. Note that all Units are connected in series and all Link Adapters are used in pairs.
Wired Master | * | Wired Slave | |
| |||
|
| * |
|
|
|
| |
Wired Slave | Link Adapter | ||
| |||
|
|
| |
|
|
|
|
|
|
|
|
* | Link Adapter | ** |
| |
|
|
| ||
** |
|
|
| * |
|
| |||
| Link Adapter | |||
|
|
| ||
|
|
|
|
|
Link Adapter | * | Link Adapter | |
| |||
|
|
| |
|
| * | |
| * |
| |
Wired Slave | Wired Slave | ||
| |||
|
|
|
*
**Optical fiber (APF/PCF)
Link Adapter **
Link Adapter *
Wired Slave
* Link Adapter **
Link Adapter *
Terminator
Maximum cable length for any single section of optical cable is 20 m for
22