Operation

The initial DC current is the maximum current the charger can deliver. It will begin at the charger’s specified maximum, but will gradually decrease as the voltage increases. This is a tradeoff in wattage and is normal for the charger.

Absorption Stage

This is the second stage of charging. It is a constant-voltage stage. Current varies as needed to maintain the voltage, but will typically decrease to a very low number over time. This “tops off the tank”, leaving the batteries at essentially 100% of capacity.

Target point: absorb setpoint or Absorb Voltage setting.

Time limit: absorb time limit or Absorb Time setting. This timer counts down from the inception of the Absorption stage until it reaches zero. The timer can be viewed. (See the system display manual.)

For multiple inverters only:

The charging of multiple stacked inverters is synchronized and is governed by the master. When the master inverter reaches the end of Absorption (and other stages), the slaves will exit Absorption as well, even if their timers have not expired. The remaining time for the slaves will be retained in the timer for each inverter.

The Absorption timer does not reset to zero when AC power is disconnected or reconnected. It only resets to zero if it runs out, or if an external STOP BULK command is sent. The rest of the time, it retains any remaining time. It adds more time to the Absorption period whenever the batteries fall below a certain voltage. (See page 21 for more information on how the timer works.)

If the voltage exceeds the Absorption voltage setting (usually due to another charging source), the inverter(s) can sell current to the loads (or the source) in an effort to bring the voltage down to the set point. This will reduce the inverter’s draw from the AC source.

Sell

This is not a charging stage and is only used once the batteries are recharged. Sell is a constant-voltage mode of operation. The inverter cannot import current to charge the batteries to this value, but it can export any excess current to hold them at a constant voltage. (Usually excess current comes into the batteries from a PV array, wind turbine, or similar renewable source.)

Target point: sell re volts or Sell Voltage setting. The default setting is 13.0 Vdc (in a 12-volt system).

This setting is typically lower than the Float voltage setting. Although the batteries are not discharged, they are maintained at a somewhat lower voltage so that the maximum amount of power can be exported.

Excess power is sent first to any loads on the inverter’s output, in what is known as “zeroing”. If the exported power exceeds the loads, the remainder is sold back to the utility grid, using the inverter’s AC input terminals. The unit will maintain this activity for as long as excess power is available. If excess power is not available, the battery voltage will drop below the Sell voltage and the unit will leave this stage.

See page 24 for more notes on the Sell function.

900-0112-01-00 Rev B

19

Page 21
Image 21
Outback Power Systems GFX1424E, GFX1312E, GFX1448E manual Absorption Stage, Sell

GFX1448E, GFX1424E, GFX1312E specifications

Outback Power Systems has long been recognized for its innovation and reliability in the field of renewable energy solutions, particularly with its GFX series of grid-tied inverters. The GFX1312E, GFX1424E, and GFX1448E models exemplify their commitment to quality and performance, making them ideal choices for both residential and commercial applications.

The GFX1312E is designed to deliver a solid 1300 watts of continuous output power at 12 volts, offering efficient energy conversion for smaller solar setups or off-grid living situations. Its compact design allows for easy installation, while advanced engineering ensures high performance even in challenging conditions. The GFX1312E features a pure sine wave output, which is critical for sensitive electronic devices, ensuring compatibility and safeguarding against potential damage.

Moving up in power capacity, the GFX1424E operates at 1400 watts with a 24-volt configuration. This model is particularly well-suited for medium-sized solar energy systems. It supports 120/240 volts split-phase output, providing greater flexibility for various household appliances and ensuring that users can maximize their energy usage with efficiency. The GFX1424E also incorporates an extensive array of intelligent charging profiles that optimize battery performance and longevity.

The GFX1448E caps the series with impressive 1400 watts of continuous output at 48 volts, catering primarily to larger installations and those requiring more robust energy management solutions. This inverter is equipped with Outback's patented GridZero™ technology, allowing for seamless integration of solar energy production with utility power, helping users to minimize grid dependence while maximizing savings. With advanced features like backup capability and grid-interactive operation, this model is highly versatile.

All three models share key characteristics such as network connectivity through the Outback Power's MATE series of controllers, enabling real-time monitoring and system management. They are designed for durability and have protective features against overloads and short circuits, ensuring reliable performance over time. With their modular design, users can easily scale their system by connecting multiple units, making these inverters a practical choice for expanding energy needs.

In summary, the Outback Power Systems GFX1312E, GFX1424E, and GFX1448E inverters provide top-tier options for those looking to harness solar energy efficiently. Their respective power outputs, advanced technologies, and user-friendly interfaces position them as excellent choices for both residential and commercial energy solutions, underscoring Outback's reputation as a leader in the renewable energy market.