Fire alarm systems

Fire alarm systems

External Fire Brigade

Panel 1826

Control and indicating panel for the fire brigade personnel

Built-in printer (option)

Ext. Fire Brigade Panel

This unit is intended to be used by the fire brigade personnel, i.e. for pre-warning, co- incidence, fire and heavy smoke / heat alarm

presentation. Point or zone alarm presentation and fire alarm reset are as in the c.i.e. it is connected to. You can scroll amongst two or more alarms in the system. All or selected alarms will be presented in the unit's display (LCD, 2x40 characters with back-light). An alarm text will be presented together with each alarm, if programmed in the c.i.e. Furthermore, > 617 texts for selected alarms can be stored in the unit and will in such a case be shown, instead of the texts sent from the c.i.e. for these alarms. A built-in buzzer will sound like in the c.i.e. Any fault in the system will be presented as "General fault in system" and the buzzer will sound. The unit is power supplied via the c.i.e. or ext. power supply.

LEDs, push buttons etc.

The unit has the following LEDs:

Fire and Alarms queued, indicating pre-warning,co-incidence, fire and heavy smoke / heat alarm.

Operation, indicating that the unit is connected to a c.i.e. and power supplied, i.e. it is in operation.

Extinguishing, indicating activated output for Extinguishing equipment.

Ventilation, indicating activated output for Ventilation equipment.

Fire brigade tx, indicating activated output for Fire brigade tx (routing equipment).

The unit has the following push buttons:

Alarms queued, used to scroll amongst the alarms.

Silence buzzer, used to silence the buzzer (it will re-sound for a new alarm.

Silence alarm devices, used to silence the alarm devices (they will re-sound for a new alarm.

Reset, used to reset the fire alarms.

Ext. Fire Brigade Panel, used for paper feed, when the unit is provided with a printer 1835 (option).

The designation texts on the front are in 1826SE in Swedish but a neutral front for other languages is available (1826CC).

Ext. FBP 1826 & Printer 1835

The ext. FBP 1826 consists of a grey metal cabinet with a door. A key is required to open the door, which has a Plexiglas in front of the FBP front, see photo. It has cable inlets on the top, bottom and back sides and is intended to be wall mounted. Two compression glands are attached.

A Printer 1835 can be mounted in the ext. FBP 1826. It will print all the alarms, including the alarm texts.

SW mode and address setting

The display and the push buttons are used to set the SW mode and address, see the opposite side of this page.

Product application

The 1826 unit is intended for indoor use and in dry premises. SW mode 1826/28 – 1587 2nd Cab is intended to be used in the systems EBL512 and EBL128 and SW mode 1826/28 – 1582 2nd Cab in the systems EBL500 / 512 / 1000 / 2000.