11.2 Heating Operation
11.2.1Outdoor fan control
∙When heating operation is enabled, based on outdoor ambient temperature, fan motor control will be adjusted according to figure below for Heating overload control:
11.2.2Heating Room Temp Sampling Control
∙To improve the judgment accuracy, indoor room temperature sampling starts when any indoor unit has stopped capability supplied (heating
∙To prevent discharge temperature drop at indoor units which is ON when sampling the room temperature of heating
∙However, if indoor room temperature is much higher compare to remote control setting temperature, before
11.2.3Powerful Operation 2
∙During cooling / heating operation, this control is to provide fast cooling / heating operation compare to normal operation.
∙Operation start if all condition below are complied: o Powerful operation ON for indoor unit.
o Not under Annual Cooling control.
∙Operation content:
o Outdoor fan speed will adjust automatically.
o Compressor frequency will adjust automatically.
∙Operation stop when comply either one of the follow conditions: o When the powerful operation is OFF for all indoor units.
o When annual cooling control activated.