30

12.1.4.2 Automatic Operation

This mode can be set using remote control and the operation is decided by remote control setting temperature,
remote control operation mode, indoor intake air temperature and outdoor air temperature.
During operation mode judgment, indoor fan motor (with speed of Lo-) and outdoor fan motor are running for 30
seconds to detect the indoor intake and outdoor air temperature. The operation mode is decided based on below
chart.
Every 30 minutes, the indoor and outdoor temperature is judged. Based on remote control setting temperature,
the value of T1 will increase up to 50°F, T2 will decrease by 37.4°F and T3 will decrease up to 46.4°F.
The Auto Operation Mode shifting will take place whenever operation mode changed from Cool/Soft Dry to
Heating or vice versa.

12.2 Indoor Fan Motor Operation

12.2.1 Basic Rotation Speed (rpm)

Manual Fan Speed
[Cooling, Dry]
o Fan motor’s number of rotation is determined according to remote control setting.
Remote control
Tab Hi Me+ Me Me- Lo
[Heating]
o Fan motor’s number of rotation is determined according to remote control setting.
Remote control
Tab Shi Me+ Me Me- Lo
Auto Fan Speed
[Cooling, Dry]
o According to room temperature and setting temperature, indoor fan speed is determined automatically.
o The indoor fan will operate according to pattern below.
o During operation, indoor fan motor may stop due to odor prevention.