Functions of Computer Communication Unit

FP2−CCU

1.3Restrictions on Units Combination

1.3Restrictions on Units Combination

1.3.1Restrictions on Current Consumption

The power supply (5 V DC) used to drive the internal circuits of the Computer Communication Unit and other units is provided from the power supply unit, through the backplane.

The overall current consumption, including the current used by other units, should not exceed the rated capacity of the power supply unit.

Unit name

Part No.

Current consumption (at 5 V DC)

 

 

 

FP2 Computer Communication Unit

FP2−CCU

60 mA or less

 

 

 

For information on the internal current consumptions of other units, please refer to the “FP2/FP2SH Hardware Manual” and the manuals of the pertinent units.

1.3.2Restrictions on Installation Position

The Computer Communication Unit can only be installed on the CPU backplane side. It should not be installed on the expansion backplane. Also, it should be installed to the right of the power supply unit and the CPU unit.

CPU backplane

Computer

Communication Unit

Can be installed only on the CPU backplane

Expansion cable

Expansion backplane

1 − 6