Names and Functions of Parts

FP2−CCU

2.1Names and Functions of Parts

2.1.2Operating Status LEDs

These display the operating status of the unit, such as communication conditions and error/alarm situations.

Display

 

 

Operation

ALARM (red)

 

Lighted: Unit error (lights on watchdog timer error)

 

 

 

 

 

 

Not lighted: Goes out when there is no error

COM. 1

SD (green)

 

Flashes while data is being sent

 

Send Data monitor

 

 

 

 

 

Goes out when no data is being sent

 

RD (green)

 

Flashes while data is being received

 

Receive Data monitor

 

 

 

 

 

Goes out when no data is being received

 

ERR (red)

 

Lights if communication error occurs

 

Communication error

 

 

 

 

 

Goes out if normal frame is received

COM. 2

SD (green)

 

Flashes while data is being sent

 

Send Data monitor

 

 

 

 

 

Goes out when no data is being sent

 

RD (green)

 

Flashes while data is being received

 

Receive Data monitor

 

 

 

 

 

Goes out when no data is being received

 

ERR (red)

 

Lights if communication error occurs

 

Communication error

 

 

 

 

 

Goes out if normal frame is received

LED status (

: Lighted

: Flashing

: Not lighted)

Tip

The communication error (ERROR LED) lights if a parity, framing, overrun, or BCC error occurs.

2 − 4