Service and Care
REMKO PWW units require virtually no maintenance when operated normally. They should, however, be checked regularly and, if necessary, cleaned, to ensure proper operation.
Important precautions prior to maintenance work
Perform the following steps prior to all service work:
1.Separate all poles of the unit from the power supply and secure it from being switched on by unauthor- ised persons.
It is not adequate to switch the unit off via the control switch on the switching unit!
2.Wait until the fan stops.
3.Turn off the flow of water and secure it from being opened on by unauthorised persons.
4.Wait until the
Do not flood the motor and the housing. Do not damage or bend the fan blades or plate fins.
Cleaning materials
◊Only clean the unit when dry or with a slightly moist towel and a soap solution.
◊Never use
◊Do not use abrasive cleaners or cleaners that con- tain solvent.
◊Even when the unit is extremely dirty, only use suit- able cleaning materials.
General care
◊Keep the inside and outside of the unit free of dust and other deposits.
◊Keep the air intake and outlet openings from being blocked.
◊Check the protection grilles and the
◊Inspect any mounted filters. Clean or exchange if necessary.
Cleaning the unit
1.Clean the air intake openings and the air outlet plate fins.
2.Clean the fan blades.
If necessary, dismantle the motor or protective grille beforehand.
3.Clean the fins of the
4.Remove extreme dirt on the fan and plate fins with a soap solution.
5.Mount the motor or the protective grille with the fan. Make sure that the distance between the fan blades and the housing is the same all the way around.
6.Clean or replace the pocket filter (accessory) if there is one.
7.To do this, loosen the screws of the filter housing and take the filter out.
Maintenance
Replacing the fan
1.Disconnect the electrical connection of the motor.
2.Remove the protective grille with the fan from the unit housing.
3.Remove the fan from the protective grille.
4.Mount the new fan on the protective grille.
5.Reattach the protective grill with the fan to the unit housing.
6.Reconnect the motor.
Replacing the heat-exchanger
1.Disconnect the electrical connection of the motor.
2.Drain the
3.Remove the accessories on the air intake and outlet sides and take the unit out of the bracket (mount).
4.Remove the rear wall with the fan.
5.Loosen the attachment screws of the heat- exchanger and take out the
6.Insert the new
7.Reconnect the motor.
Inspection following maintenance:
◊The fan wheel must be able to rotate freely in the fan housing.
◊The distance between the fan blades and the fan housing must be the same.
◊The motor must rotate in the direction of the arrow.
◊After service and maintenance is complete, an elec- trical safety test must be conducted in accordance with VDE 0701.