Panasonic manual Technical Data, PWW 4000 series, Type, 4030, 4050, 4080, 4100

Models: PWW 4000

1 16
Download 16 pages 8.69 Kb
Page 9
Image 9

Technical Data

PWW 4000 series

 

 

 

 

 

 

 

 

 

 

Type

 

4030 - 3

4030 - 4

4050 - 3

4050 - 4

 

 

 

 

 

 

Electrical connection

V

400 / 3~ N

400 / 3~ N

400 / 3~ N

400 / 3~ N

Frequency

Hz

50

50

50

50

Power consumption

kW

0.13

/ 0.10

0.13

/ 0.10

0.26

/ 0.18

0.26

/

0.18

Rated current

A

0.26

/ 0.16

0.26

/ 0.16

0.52

/ 0.29

0.52

/

0.29

Speed

U/min

1340

/ 1040

1340

/ 1040

1360

/ 1020

1360

/

1020

Air capacity

m³/h

2050

/ 1640

1850

/ 1500

3400

/ 2870

3150

/

2770

Sound pressure level 1)

dB(A)

53

/ 48

55

/ 49

55

/ 51

58

/

54

Heating medium connection

inch

R1"

R1¼"

R1"

R1¼"

 

 

 

 

 

 

Heating medium

 

Pump warm water or pump hot water up to max. 130 °C

Operating pressure

bar

16

 

 

 

16

16

16

Weight

kg

26

27

34

36

 

 

 

 

 

 

 

 

 

1) Measurement at intervals of 5 m, measuring room volume 800 m³, average reverberation time 1.4 s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PWW 4000 series

 

 

 

 

 

 

 

 

 

 

Type

 

4080 - 3

4080 - 4

4100 - 3

4100 - 4

 

 

 

 

 

 

Electrical connection

V

400 / 3~ N

400 / 3~ N

400 / 3~ N

400 / 3~ N

Frequency

Hz

50

50

50

50

Power consumption

kW

0.42

/ 0.28

0.42

/ 0.28

0.76

/ 0.47

0.76

/

0.47

Rated current

A

0.76

/ 0.46

0.76

/ 0.46

1.50

/ 0.81

1.50

/

0.81

Speed

U/min

880

/ 670

880

/ 670

870

/ 650

870

/

650

Air capacity

m³/h

5400

/ 4300

4730

/ 4700

8250

/ 6620

7670

/

6180

Sound pressure level 1)

dB(A)

55

/ 49

55

/ 49

58

/ 54

59

/

55

Heating medium connection

inch

R1¼"

R1¼"

R1½"

R1½"

 

 

 

 

 

 

Heating medium

 

Pump warm water or pump hot water up to max. 130 °C

Operating pressure

bar

16

 

 

 

16

16

16

Weight

kg

47

51

60

68

 

 

 

 

 

 

 

 

 

 

 

1) Measurement at intervals of 5 m, measuring room volume 800 m³, average reverberation time 1.4 s

9

Page 9
Image 9
Panasonic manual Technical Data, PWW 4000 series, Type, 4030, 4050, 4080, 4100