Environmental Specifications

Appendix A: PowerStation Specifications

Environmental Specifications

Environmental Specifications

Even though the PA PowerStation is built to withstand harsh environments, limit the PowerStation’s exposure to adverse conditions such as dust, oil, moisture, and corrosive vapors to minimize maintenance and repair costs.

Remember that the temperature within a protective enclosure is generally higher than the external temperature. Thus, if the PA PowerStation is operating inside an enclosure at temperature levels above its rated ambient temperature, you must cool the enclosure.The PowerStation conforms to the environmental specifications listed in Table A-7.

Table A-7: Environmental Specifications Chart

Category

Specifications

 

 

Operating

32 to 122oF (0 to 50oC) ambient (air temp. outside

Temperature

of PA backshell)

 

 

 

Storage

-4 to 140oF (-20 to 60oC)

Temperature

 

 

 

 

Relative Humidity

0% to 95% non-condensing

 

 

 

Shock Rating

10g peak; 11ms (operating)

30g peak; 11ms (non-operating)

 

 

 

Operating Vibration

5-500Hz: 1.0 grms random

 

 

 

 

Faceplate

Tested for UL Type 4/4X Environment

Design

 

 

 

Warning: The PowerStation is rated NEMA Type

 

4/4X only if it is installed in a NEMA 4/4X rated

 

enclosure.

 

 

 