RECOMMENDED WIRING DISTANCES

Refer to Table C for the recommended maximum distances (transformer to load), which are calculated with a 10 percent voltage drop. Distances are calculated in feet; values in parentheses are in meters.

Table C. Recommended Wiring Distances

Voltage

Total VA

 

Wire Gauge

 

Consumed

20 AWG (0.5 mm2)

18 AWG (1.0 mm2)

16 AWG (1.5 mm2)

 

 

10

333 ft (101 m)

529 ft (161 m)

840 ft (256 m)

 

 

 

 

 

26 Volts

20

166 ft (50 m)

264 ft (80 m)

420 ft (128 m)

 

 

 

 

30

111 ft (33 m)

176 ft (53 m)

280 ft (85 m)

 

 

 

 

 

 

 

50

66 ft (20 m)

105 ft (32 m)

168 ft (51 m)

 

 

 

 

 

POWER CONSUMPTION

Table D contains the estimated power consumption information for each model. These calculations are based on an input frequency setting of 60 Hz for 115 VAC and 50 Hz for 230 VAC.

Table D. Estimated Power Consumption

Model

Input Voltage

Input Fuse

Maximum Load

BTU/H*

 

 

 

 

 

RCS8B5/

115 VAC

1.6 A

143 W, 1.24 A

72

RCS8F5

 

 

 

 

230 VAC

1 A

143 W, 0.62 A

72

 

 

 

 

 

 

RCS16B10/

115 VAC

3 A

280 W, 2.44 A

123

RCS16F10

 

 

 

 

230 VAC

1.6 A

282 W, 1.22 A

119

 

 

 

 

 

 

RCS16B20/

115 VAC

5 A

549 W, 4.27 A

313

RCS16F20

 

 

 

 

230 VAC

3 A

542 W, 2.35 A

198

 

 

 

 

 

 

RCS32B20/

115 VAC

5 A

549 W, 4.27 A

313

RCS32F20

 

 

 

 

230 VAC

3 A

542 W, 2.35 A

198

 

 

 

 

 

 

*BTU/H values for the transformer are equal to the difference between input power and output power.