13
IntelliFlo VS-3050 Installation and User’s Guide

Connecting IntelliFlo VS-3050 to an IntelliTouch System

The IntelliFlo VS-3050 can be controlled by an IntelliT ouch system via the RS-485 communication cable
(P/N 350122). In this configuration, IntelliT ouch starts, stops and controls the speed of the IntelliFlo pump.
When the IntelliT ouch does this, it rewrites the IntelliFlo memory, which can take several seconds. This
causes a delay after a command is given on the IntelliT ouch control panel until the Intelliflo physically
responds.
The IntelliFlo control panel is disabled when communicating with the IntelliT ouch system. Note that
IntelliT ouch will not start communicating with the IntelliFlo until the appropriate pump address is assigned to
a circuit. The IntelliFlo default pump address is one. See page 6 for details about how to check the address
and change if necessary . For more information, refer to the IntelliT ouch User's Guide (P/N 520102).
T o connect the IntelliFlo communication cable to IntelliTouch load center:
1. CAUTION - Switch the main power off to the IntelliTouch load center.
2. Unlatch the IntelliT ouch load center front door spring latches, and open the front door .
3. Remove the cover-panel screws securing the high voltage cover-panel, and remove it from the
enclosure.
4. Loosen the two control panel access screws and fold down the outdoor control panel.
5. Insert the two-wire cable into plastic grommet on the bottom of the enclosure and route the wire up
through the low voltage raceway to the Personality board.
IntelliTouch Load Center
Cover-panel
screw
(Cover-panel not
shown)
Access
screw
Personality Board
Low voltage raceway
Plastic grommet