80
Set IOChannel
Set IOChannel Analog (True Analog)
active-to-inactive-delay
When the I/O is commanded to an inactive state, this is the length of the delay before
the command is executed. Valid values are 1-9999 x 100 ms. The default is 100 ms.
inactive-to-active-delay
When the I/O is commanded to an active state, this is the length of the delay before the
command is executed. Valid values are 1-9999 x 100 ms. The default is 100 ms.
active-signal-width
How long the channel output will be active during the pulse mode. Valid values are
1-9999 x 100 ms. The default is 100 ms.
inactive-signal-width
How long the channel output will remain inactive during pulse mode. Valid values are
1-9999 x 100 ms. The default is 100 ms.
failsafe-action
When there has been no I/O activity within the specified time (set in the Global
Settings) and the Failsafe Timer is triggered, you can set the Failsafe Action to:
zNone—The state of the Digital/Relay output remains the same, no change.
zActivate Output—Activates the output.
zDeactivate Output—Deactivates the output.
Description Sets the Analog input channel settings.
User Level Admin
Syntax set iochannel <analog_channel> type current|voltage
range <range_specifier>
set iochannel <analog_channel> alarm
[level 1|2|3|4|5 [mode on|off] [trigger-type disabled|low|high]
[trigger-level <decimal_value>] [clear-mode auto|manual]
[clear-level <decimal_value>] [snmp on|off] [syslog on|off]]
Options analog_channel
Specify the Analog channel number, for example, a2 or a4 (this also applies to
Temperature models).
type
Select the type of input being measured, either Current or Voltag e. The default is
Current.
range
Select the range for the measurement type. For current, the range is:
z0-20 (0-20mA) This is the default.
z4-20 (04-20mA)
For voltage, the range is:
z1 (+/-1V)
z5 (+/-5V)
z10 (+/-10V) This is the default.
z150 (+/-150mV)
z500 (+/-500mV)