Perle Systems TS2, DS1 manual Level

Models: DS1 TS2

1 88
Download 88 pages 61.31 Kb
Page 82
Image 82

Set IOChannel

level

You can specify up to five alarm trigger/clear severity levels. If the Trigger Type is Low, an alarm is triggered when the input drops below the specified Trigger value; other severity level trigger values must decrease in value with each subsequent level. If the Trigger Type is High, an alarm is triggered when the input is higher than the specified Trigger value; other severity level trigger values must increase in value with each subsequent level. To clear an alarm, the input must drop below the specified value when Trigger Type is High or go above the specified value when Trigger Type is Low.

mode

Enables/disables an alarm level. The default is off.

trigger-type

If the Trigger Type is Low, an alarm is triggered when the input drops below the specified Trigger value; other severity level trigger values must decrease in value with each subsequent level. If the Trigger Type is High, an alarm is triggered when the input is higher than the specified Trigger value; other severity level trigger values must increase in value with each subsequent level.

trigger-level

Specify the value that will trigger an alarm, the measurement is based on the Type and Range that you specify. This value must not fall within the scope of the value used to clear an alarm.

clear-mode

Specifies whether an activated alarm must be Manually cleared, or can be cleared when the input drops below the specified value (when Trigger Type is High) or goes above the specified value (when Trigger Type is Low).

clear-level

Specify that value that will clear an alarm, the measurement is based on the Type and Range that you specify. This value must not fall within the scope of the value used to trigger an alarm.

snmp

Sends an SNMP trap when an alarm is triggered or cleared. The trap consists of the severity level and whether the alarm was triggered or cleared.

syslog

Sends a message to syslog when an alarm is triggered or cleared. The syslog entry includes the severity level and the value that caused the alarm to trigger or clear. The syslog message is associated with Level Critical.