HID-PrimaVision SON and CDO

Electrical installation notes

 

Mains operation

 

Rated mains voltage

220 - 240 V

With tolerances for performance

203 - 254 V

+6%-8

 

With tolerances for operation

180 - 264 V

Mains frequency

50/60 Hz

Power factor

> 0.98

Earth leakage current

< 0.5 mA per driver

Overvoltage protection

48 hrs at 325 Vac

 

2 hrs at 366 Vac

 

5 min. at 400 Vac

Lamp operation

 

Operation frequency (typical)

125 Hz

Ignition voltage 100/150W

3 - 4 kV

70W

2 - 2.5 kV

Cable capacity

 

SON

Max. 1 nF

CDO

Max. 200 pF

Air and creepage distance from any

> 4 mm

(metal) part that may become live,

 

to earthed environment (class I) or

 

test finger (class II)

 

Notes:

1.With three-phase mains supply, neutral should never be disconnected; otherwise circuitry could be damaged.

2.For proper EMC, wiring inside luminaire should be as straight and as short as possible; mains wires should not run parallel to lamp wires.

3.Driver should be mounted in luminaire > min IP 23.

4.Thermo-protected circuit incorporates self-resetting facility; ignition attempts stop after 7 min.; mains supply must be switched off and on to reset driver.

5.Automatic restart after lamp replacement or voltage dip, lamp may take up to 18 min. to restart.

6.Insulation resistance test: 500 Vdc from Line/Neutral to Earth (not between Line and Neutral). Ensure that the Neutral is reconnected again after abovementioned test is carried out and before the installation is put into operation.

Inrush current

Conversion table for max. quantities of drivers on other types of Miniature Circuit Breaker

MCB type

Rating

Relative number of

 

 

drivers

B

16 A

100% (see table

 

 

above)

B

10 A

63%

C

16 A

170%

C

10 A

104%

L, I

16 A

108%

L, I

10 A

65%

G, U, II

16 A

212%

G, U, II

10 A

127%

K, III

16 A

254%

K, III

10 A

154%

Notes:

 

 

1.Data is based on a mains supply with an impedance of 400 mΩ

(equal to 15 m cable of 2.5 mm2and other 20 m to the middle of the power distribution), under worst case conditions.With an impedance of 800 mΩ the number of drivers can be increased by 10%.

2.Measurements will be verified in real installations; therefore data are subject to change.

3.In some cases the maximum number of drivers is not determined by the MCB but by the maximum electrical load of the installation.

4.Note that the maximum number of drivers is given when these are all switched on at the same moment, i.e. by a wall switch.

5.Measurements were carried out on single-pole MCB’s. For multi- pole MCB’s it is advisable to reduce the number of drivers by 20%.

6.The maximum number of drivers which can be connected to one Residual Current Detector of 30 mA is 30.

Mechanical installation notes

 

Wire cross-section:

 

 

On the mains side

0.75…2.5 mm2

advised rating: Uo/U

 

 

= 250/250V

On the lamp side

0.75…2.5 mm2

advised rating: Uo/U

 

 

= 250/250V

Strip length

6 mm

 

HID-PV

3.106 OEM Catalogue 2009/2010

Page 106
Image 106