HID-DynaVision Control SON
Electrical installation notes |
|
|
|
| Control characteristics |
| ||
Mains operation |
|
|
|
| Control input |
| ||
Rated mains voltage | 220 - 240 V | Control voltage input | ||||||
With tolerances for performance | 203 - 254 V | Protected against mains voltage | Yes | |||||
With tolerances for operation | 180 - 264 V | connection |
| |||||
Mains frequency | 50/60 Hz | Control resistance (to be | 0 - 100 kΩ | |||||
Operation frequency (typical) | 50 Hz | connected on |
| |||||
Power factor* (nominal power) | > 0.92 |
|
|
| Regulating light level SON | 20 - 100% | ||
Power factor* (35% power) | > 0.7 |
|
|
| 250/400 W |
| ||
* With rated PF capacitor value |
|
|
|
| After ignition or lamp restrike allways 100% level for 5 min | |||
Earth leakage current (per gear) | < 0.5 mA | Gear dimming fading rates are: |
| |||||
Overvoltage protection | 48 hrs at 325 Vac | SON 250/400 W |
| |||||
|
|
| 2 hrs at 366 Vac | Fade up | < 1.0 min | |||
|
|
| 5 min at 400 Vac | Fade down | < 1.5 min | |||
Cable length to normal gear | No limit. |
|
| |||||
Notes: |
|
|
|
| Mechanical installation notes |
| ||
1.With | Wire |
| ||||||
disconnected; otherwise circuitry could be damaged. | On the mains side | 0.75…2.5 mm2 | ||||||
2. Gear must be earthed. |
|
|
|
| On the lamp side | 0.75…2.5 mm2 | ||
3. Power factor correction capacitor should be connected directly | Strip length | 6 mm | ||||||
on the mains; when installing this device in front of existing gear, the |
|
| ||||||
original capacitor has to be removed. |
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|