Philips 380-400-415V, 220-230-240V manual Control input

Models: 220-230-240V 380-400-415V

1 172
Download 172 pages 24.56 Kb
Page 114
Image 114
Relative number of drivers
100% (see table above)

HID-DynaVision DALI SON and CDO

Control characteristics

 

Control input

DALI

Input is protected against mains voltage connection

Dimming fading rates are implemented to guarantee optimal lamp Behaviour for SON Lamps:

Run up time before dimming*

5 minutes

Fade down time** (100%-20%)

< 1.5 minutes

Fade up time** (20%-100%)

< 1 minute

Power indication

35 - 100%

Corresponding light level (see

20% - 100%

graph)

 

Behaviour for CDO Lamps:

 

Run up time before dimming*

10 minutes

Fade down time** (100%-60%)

< 1.5 minutes

Fade up time** (60%-100%)

< 1 minute

Power indication

60 - 100%

Regulating light level (see graph)

50% - 100%

*EMC attention should be given with cable > 3 mtr.

**Run-up time, and fading down/up rates are determined to guarantee reliable lamp operations.

Inrush current

Conversion table for max. quantities of drivers on other types of Miniature Circuit Breaker

MCB type

Rating

Notes:

1.Data is based on a mains supply with an impedance of 400 mΩ

(equal to 15 m cable of 2.5 mm2and other 20 m to the middle of the power distribution), under worst case conditions.With an impedance of 800 mΩ the number of drivers can be increased by 10%.

2.Measurements will be verified in real installations; therefore data are subject to change.

3.In some cases the maximum number of drivers is not determined by the MCB but by the maximum electrical load of the installation.

4.Note that the maximum number of drivers is given when these are all switched on at the same moment, i.e. by a wall switch.

5.Measurements were carried out on single-pole MCB’s. For multi- pole MCB’s it is advisable to reduce the number of drivers by 20%.

6.The maximum number of drivers which can be connected to one Residual Current Detector of 30 mA is 30.

Mechanical installation notes

 

Wire cross-section:

 

 

On the mains side

0.75…2.5 mm2

advised rating: Uo/U

 

 

= 250/250V

On the lamp side

0.75…2.5 mm2

advised rating: Uo/U

 

 

= 250/250V

Strip length

6 mm

 

B

 

16 A

 

 

 

 

 

 

 

 

 

 

 

B

 

10 A

63%

 

 

C

 

16 A

170%

 

 

C

 

10 A

104%

 

 

L, I

 

16 A

108%

 

 

L, I

 

10 A

65%

 

 

G, U, II

 

16 A

212%

 

 

G, U, II

 

10 A

127%

 

 

K, III

 

16 A

254%

 

 

K, III

 

10 A

154%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HID-DV DALI