Philips 220-230-240V, 380-400-415V manual +6%-8%

Models: 220-230-240V 380-400-415V

1 172
Download 172 pages 24.56 Kb
Page 113
Image 113

HID-DynaVision DALI SON and CDO

 

 

A2

B1

B2

D1

 

 

 

 

A3

 

C1

 

 

 

A1

HID-DV

Type

A1Nom

A2Nom

A3Nom

B1Nom

B2Nom

C1Nom

D1Nom

 

 

 

 

 

 

 

 

HID-DynaVision DALI

150.0

134.0

136.0

90.0

70.0

40.0

4.5

 

 

 

 

 

 

 

 

HID Gear

Inrush current

Type

Maximum

Inrush

Inrush

 

gear number

current

current

 

on MCB

Peak

Width

 

(x)

(A)

(ms)

 

 

 

 

HID-D DALI 100-150 /S CDO/SON/SDW

6

50

0.45

 

 

 

 

Electrical data

Type

Number

Rated

Line

Line

T-case

T-case

T-ambient

Ignition

Cable-Cap

 

of

Gear-

Frequency

Voltage

life

maximum

 

Voltage

outputwires

 

Lamps

Lamp

 

 

 

 

 

 

mutual

 

(x)

Power

(Hz)

(V)

(ºC)

(ºC)

 

(kV)

(pF)

 

 

 

 

 

 

 

 

 

 

HID-D DALI 100-150 /S CDO/SON/SDW

1

100-150

50/60

220-240

90

100

45

4.00

1000

 

 

 

 

 

 

 

 

 

 

Ordering and packing data

Type

EAN code

Weight

Qty bulk

Dimensions bulk packing

EAN code

EOC

 

1 piece

 

packing

 

bulk packing

8711500

 

 

 

 

 

 

 

HID-D DALI 100-150 /S CDO/SON/SDW

8711500928733

0.725 kg

10

39.8 cm x 16 cm x 11.1 cm

8711500928740

928733 30

 

 

 

 

 

 

 

Electrical installation notes

 

Notes:

Mains operation

 

1.With three-phase mains supply, neutral should never be

Rated mains voltage

220-240 V

disconnected; otherwise circuitry could be damaged.

With tolerances for performance

203-254 V

2. For proper EMC, wiring inside luminaire should be as straight and as

+6%-8%

 

short as possible; mains wires should not run parallel to lamp wires.

With tolerances for operation

180-264 V

3. Driver should be mounted in luminaire >min IP 23.

Mains frequency

50/60 Hz

4.Thermo-protected circuit incorporates self-resetting facility; ignition

Power factor 100% power

>0.98

attempts stop after seven minutes; mains supply must be switched off

Power factor 35% power

>0.93

and on to reset driver.

Earth leakage current

<0.2 mA per driver

5. Insulation resistance test: 500 Vdc from Line/Neutral to Earth (not

Overvoltage protection

48 hrs at 325 Vac

between Line and Neutral). Ensure that the Neutral is reconnected

 

2 hrs at 366 Vac

again after abovementioned test is carried out and before the

 

5 min. at 400 Vac

installation is put into operation.

Lamp operation

 

 

Operation frequency (typical)

125 Hz

 

Ignition voltage

3-4 kV

 

Cable capacity

 

 

SON-100-150W lamps (2.7 kV)

Max. 1 nF

 

CDO-lamps (3.3 kV)

Max. 0.5 nF

 

Air and creepage distance from any

>4 mm

 

(metal) part that may become live,

 

 

to earthed environment (class I) or

 

 

test finger (class II)

 

 

OEM Catalogue 2009/2010

3.113

Page 113
Image 113