Polaris PG10* 50-175-3NV OR 3PV, PR 199-100-3NV OR 3PV VERTICAL TERMINATIONS 175,000+ BTU/HR

Models: PG10* 50-175-3NV OR 3PV PR 199-50 3NV OR 3PV PG10* 34-150-2NV OR 2PV PR 100-34 2NV OR 2PV PG10* 100-199-3NV OR 3PV PG10* 34-100-2NV OR 2PV PR 130-50 2NV OR 2PV PR 130-34 2NV OR 2PV PG10* 34-130-2NV OR 2PV PG10* 50-130-2NV OR 2PV PR 175-50 3NV OR 3PV PR 150-34 2NV OR 2PV PG10* 50-199-3NV OR 3PV PR 199-100-3NV OR 3PV

1 32
Download 32 pages 63.46 Kb
Page 13
Image 13
VERTICAL TERMINATIONS (175,000+ BTU/HR)

VERTICAL TERMINATIONS (175,000+ BTU/HR)

For inputs of 175,000 BTU/Hr or greater, all termination pip- ing and fittings are 3”. Do not reduce before penetrating the wall.

The vertical inlet air termination requires a return bend or two short or long sweep radius 90° elbows to keep the inlet downward and prevent entry of rain. These elbows are con- sidered part of the termination and should not be included when calculating the maximum allowable vent pipe length. Refer to figure 9B for the proper location of the air inlet with respect to the exhaust outlet termination. The vertical exhaust outlet termination is a 3 inch pipe which terminates at least 12 inches above the inlet air termination.

The air inlet and exhaust outlet terminations must be at least 12 inches above the roof line or anticipated snow levels as shown in figure 9B below.

Note: See “Venting Additional Polaris® Units” below if installing more than one Polaris® gas water heater.

Figure 9B: Vertical Termination (175,000+ BTU/Hr models)

*100 Gallon Model Shown.

Venting Additional Polaris® Units (175,000+ BTU/Hr Models)

When using two (2) Polaris® units, install vent terminations using either Method A or Method B below:

When using three or more Polaris® units, install vent terminations per Method C or Method D:

13

Page 13
Image 13
Polaris PG10* 50-175-3NV OR 3PV, PR 199-100-3NV OR 3PV, PG10* 50-199-3NV OR 3PV VERTICAL TERMINATIONS 175,000+ BTU/HR