Models: PG10* 50-175-3NV OR 3PV PR 199-50 3NV OR 3PV PG10* 34-150-2NV OR 2PV PR 100-34 2NV OR 2PV PG10* 100-199-3NV OR 3PV PG10* 34-100-2NV OR 2PV PR 130-50 2NV OR 2PV PR 130-34 2NV OR 2PV PG10* 34-130-2NV OR 2PV PG10* 50-130-2NV OR 2PV PR 175-50 3NV OR 3PV PR 150-34 2NV OR 2PV PG10* 50-199-3NV OR 3PV PR 199-100-3NV OR 3PV

1 32
Download 32 pages 63.46 Kb
Page 28
Image 28
TROUBLESHOOTING

TROUBLESHOOTING

Ignition Control Module (ICM) LED Error Codes: (Flashes visible through viewport in access door)

FLASHES

INDICATED PROBLEM

CONTROL REACTION

1

Pressure Switch Closed

SC*

2

Pressure Switch Open

SL

3

Failed Ignition

SL3

4

Gas Valve Hardware Fault

SL

5

Flame Sense Hardware Fault

SC

6

False Flame

SL**

8

Ignition Control Hardware Fault

SL

9

Ignition Control Software Fault

SL

Rapid

L1 Polarity Detection

SC

SL (Soft Lockout): Control Automatically resets after 60 minutes.

SL3 (Soft Lockout/Hard Lockout): Control automatically resets after 60 minutes, with a maximum of 3 resets, followed by hard lockout requiring service.

SC (Self Clearing): Control will function normally as soon as it no longer detects the previously indicated fault.

*when pressure switch or blower relay opens

**when flame is no longer sensed.

† Blower Isolation Relay is used on models 150,000 BTU/Hr and above.

Note: If unit goes into a soft or hard lock-out the ignition control module can be reset by cycling power to the water heater.