Polaris PR 130-50 2NV OR 2PV Vent Pipe Material, Vent Pipe Installation, Vent Pipe Length

Models: PG10* 50-175-3NV OR 3PV PR 199-50 3NV OR 3PV PG10* 34-150-2NV OR 2PV PR 100-34 2NV OR 2PV PG10* 100-199-3NV OR 3PV PG10* 34-100-2NV OR 2PV PR 130-50 2NV OR 2PV PR 130-34 2NV OR 2PV PG10* 34-130-2NV OR 2PV PG10* 50-130-2NV OR 2PV PR 175-50 3NV OR 3PV PR 150-34 2NV OR 2PV PG10* 50-199-3NV OR 3PV PR 199-100-3NV OR 3PV

1 32
Download 32 pages 63.46 Kb
Page 7
Image 7
Vent Pipe Material

Vent Pipe Material

The following plastic materials may be used for both the combustion air inlet and exhaust outlet piping subject to state and local codes:

Schedule 40 PVC or ABS

Schedule 40 or 80 CPVC

DWV Pipe is acceptable

Note: Use only solid (not foam core) piping.

Plastic pipe and fittings are available through most plumb- ing suppliers. Always check the marking on the pipe to make sure you are using the correct material.

Important: Do not use vent elbows in this vent pipe installa- tion (see figure 5 below).

Figure 5: Correct and Incorrect Pipe Fittings

Vent Pipe Installation

The following guidelines should be followed when installing the air inlet and exhaust outlet piping:

Venting should be as direct as possible with a minimum number of pipe fittings.

Vent diameter must not be reduced unless specifically noted in the installation instructions.

All 2” horizontal vent piping must be sloped upward 1/4 inch per foot (3” Piping must slope upward at 1/8” per foot) so that condensate will run back to the heater and exit through the condensate trap.

Support all horizontal pipe runs every four feet and all vertical pipe runs every six feet or according to local codes.

Vents run through unconditioned spaces where below freezing temperatures are expected should be properly insulated to prevent freezing. For horizontal runs, wrap the vent pipe with nationally recognized/listed heat tape and/or approved insulation for freeze protection. Install per the manufacturer’s instructions.

An air intake filter is included with the unit and must be installed according to the installation instructions

supplied with the filter.

The combustion air inlet and exhaust outlet piping and termination may be installed in one of the following type terminations:

1.Standard Horizontal (2 Pipe)

2.Alternate Horizontal (2 Pipe)

3.Vertical (2 Pipe)

4.Concentric Vent - Through the Wall

5.Concentric Vent - Through the Roof

All pipe, fittings, pipe cement, primers and procedures must conform to American National Standard Institute and American Society for Testing and Materials (ANSI/ASTM) standards in the United States. This water heater has been design certified by the Canadian Standards Association for use with the specified (CSA) listed plastic vent pipe.

All joints in the inlet and outlet piping must be properly cemented. Size and cut all piping before cementing.

1.Cut the pipe end square and remove all ragged edges and burrs. Make sure the inside of the pipe is clean and free of cuttings and loose dirt. Chamfer the end and apply primer to the fitting and pipe.

2.Using a suitable grade of pipe cement, apply a moder- ate, even coat inside the fitting. Apply a liberal amount of cement to the outside of the pipe to socket depth.

Note: It is important to select the proper pipe cement for the type of plastic pipe being used.

3.Assemble the parts quickly while the cement is still wet. Twist the pipe 1/4 turn during insertion and hold for 30 seconds.

Vent Pipe Length

Size the exhaust outlet and combustion air inlet pipes as specified in Table 1. This table lists the maximum allow- able length in feet of the exhaust outlet and combustion air inlet pipes as related to the number of required elbows and the termination. The specified maximum lengths are for the separate inlet and exhaust pipe systems and not the combined length of both systems. Minimum pipe length is 6 feet with one elbow per side.

1.Determine termination type and pipe size.

2.Determine number of elbows in exhaust pipe. Do not include the elbows in the termination or the condensate trap. Corresponding number Indicates the maximum length of exhaust pipe.

3.Determine number of elbows in inlet pipe. Do not include the elbows in the termination. The correspond- ing number indicates the maximum length of inlet pipe.

7

Page 7
Image 7
Polaris PR 130-50 2NV OR 2PV, PR 199-100-3NV OR 3PV Vent Pipe Material, Vent Pipe Installation, Vent Pipe Length