INSTALLATION CHECKLIST
Water Heater Location | Alternate Horizontal | |
Requirements | Correct relationship - outlet to inlet. | |
12” Min. above anticipated snow level. | ||
Centrally located with the water piping system. Located | 2” exhaust outlet/air inlet pipe sloped down towards | |
as close to the gas piping and vent pipe system as pos- | water heater at 1/4” per foot. 3” piping sloped down | |
sible. | towards the heater at 1/8” per foot. | |
Away from corners, other vents, windows, etc. | ||
Located indoors and in a vertical position. Protected | ||
| ||
from freezing temperatures. | Vertical | |
Proper clearances from combustible surfaces main- | ||
tained and not installed directly on a carpeted floor. | Inlet - 12” Min. above roof/snow level. | |
Sufficient room to service the water heater. | Correct relationship - outlet to inlet. | |
Provisions made to protect the area from water dam- | Away from corners, other vents, windows, etc. | |
age. Properly sized drain pan installed and piped to an |
| |
adequate drain. | Concentric | |
Installation area free of corrosive elements and | 12” Min. above grade/snow level. | |
flammable materials. | 2” exhaust outlet/air inlet pipe sloped down towards | |
Condensate Line | water heater at 1/4” per foot. 3” piping sloped down | |
| ||
Drain stem is fully inserted in the elbow and glued | towards the heater at 1/8” per foot. | |
Away from corners, other vents, windows, etc. | ||
properly. | ||
| ||
Trap aligned so that the exhaust pipe is in a vertical | Water System Piping | |
position close to the surface of the water heater. | ||
Line properly sloped to adequate drain or approved | Temperature and pressure relief valve properly | |
condensate pump. | ||
installed with a discharge line run to an open drain and | ||
Properly vented. | ||
protected from freezing. | ||
Protected from freezing (if required). | ||
All piping properly installed and free of leaks. | ||
Vent Pipe System | ||
Heater completely filled with water. | ||
Vent pipe and fittings of approved material. | A properly sized expansion tank must be installed on all | |
closed systems. | ||
Acceptable size, length, and number of elbows on air | ||
A tempering valve (provided) must be installed per the | ||
inlet pipe. | ||
manufacturer’s instructions. | ||
Acceptable size, length, and number of elbows on | ||
Gas Supply and Piping | ||
exhaust outlet pipe. | ||
Add the air inlet filter per the manufacturer’s instruction. | If using a flexible gas connector, make sure its rating | |
Installed in accordance with prevailing provisions of | tag matches or exceeds the input of the water heater. | |
Local codes, or in the absence of such, National Fuel | Adequate pipe size and of approved material. | |
Gas Code, NFPA 54, ANSI | Gas supply is the same type as listed on the water | |
nadian Installations must be performed in accordance | heater data plate. | |
with |
Gas line equipped with full opening | |
All 2” horizontal piping sloped down toward the water | union and drip leg. | |
heater at 1/4” per foot. 3” piping sloped down towards | Approved pipe joint compound used. | |
the heater at 1/8” per foot. |
| |
Not obstructed in any way. | proved means used to check all connections and fit- | |
tings for possible gas leaks. | ||
Vent Termination | ||
Electrical Connections | ||
Horizontal | ||
Unit connected to a dedicated power supply. | ||
Correct relationship - outlet to inlet. | Unit connected to a 120V electrical supply. | |
12” Min. above grade/snow level. | ||
Proper polarity. | ||
2” exhaust outlet/air inlet pipe sloped down towards | ||
Water heater properly grounded. | ||
water heater at 1/4” per foot. 3” piping sloped down | ||
Installed in accordance with prevailing provisions of | ||
towards the heater at 1/8” per foot. | ||
local codes, or in the absence of such, National Fuel | ||
Away from corners, other vents, windows, etc. | ||
Gas Code, NFPA 54, ANSI | ||
| ||
| Canadian installations must be performed in accor- | |
| dance with |
23