Powermatic OES9138 Adjustments, Test Run After Wiring, Converting to 460 Volt, Extension cords

Models: OES9138

1 32
Download 32 pages 49.38 Kb
Page 11
Image 11

Test Run After Wiring

On the three-phaseunit, after wiring has been completed, you should check that the wires are connected properly:

1.Connect machine to power source and press the start button (A, Figure 8).

2.The sanding belt should move left to right, as viewed from the front of the machine. If the sanding belt movement is incorrect, press the stop button (B, Figure 8) and disconnect machine from power.

3.Switch any two of the three wires at "R,S,T".

4.Reconnect machine to power source.

Converting to 460 Volt

Refer to the diagrams on pages 31 and 32 for connecting the motor leads for 460 volt power. Also convert to a 460V switch. If using a plug, it must be a proper UL/CSA listed 460 volt plug. The edge sander must comply with all local and national codes after being wired.

If hard-wiring directly to a control panel, follow the same safety recommendations mentioned under “230 Volt Operation.”

Extension cords

An extension cord is not recommended for this machine, but if one is necessary, make sure the cord rating is suitable for the amperage listed on the machine’s motor plate. An undersized cord will cause a drop in line voltage resulting in loss of power and overheating.

Use the chart in Figure 9 as a general guide in choosing the correct size cord. If in doubt, use the next heavier gauge. The smaller the gauge number, the heavier the cord.

Adjustments

Main Table Positioning

The main table can be raised or lowered to suit your workpiece, and is designed on a special balance mount so that smooth adjustment is achieved by a simple push or pull on the table.

To adjust, loosen the locking handles (A, Figure

10)and move the table to desired position by hand, then tighten locking handles (A, Figure

10).

If the table is in low position, it may spring up suddenly when the locking handles are loosened.

Figure 8

Recommended Gauges (AWG) of Extension Cords

 

 

 

Extension Cord Length *

 

 

 

 

 

 

 

 

 

Amps

25

50

75

100

150

200

feet

feet

feet

feet

feet

feet

 

 

 

 

 

 

 

 

< 5

 

16

16

16

14

12

12

 

 

 

 

 

 

 

 

5 to

8

16

16

14

12

10

NR

 

 

 

 

 

 

 

8 to 12

14

14

12

10

NR

NR

 

 

 

 

 

 

 

 

12 to

15

12

12

10

10

NR

NR

 

 

 

 

 

 

 

 

15 to

20

10

10

10

NR

NR

NR

 

 

 

 

 

 

 

 

21 to

30

10

NR

NR

NR

NR

NR

 

 

 

 

 

 

 

 

*based on limiting the line voltage drop to 5V at 150% of the rated amperes.

NR: Not Recommended.

Figure 9

Figure 10