Specifications

Table 3. Battery

Configuration

300 VA: (1) 12V, 4.2 Ah or (2) 6V, 4.0 Ah internal battery(s)

 

550 VA: (1) 12V, 7.0 or 7.2 Ah internal battery

 

700 VA: (1) 12V, 9 Ah internal battery

Voltage

12 Vdc

Type

Sealed, maintenance-free, valve-regulated, lead-acid

Charging

8 hours to 95% capacity with output fully loaded

Monitoring

Advanced monitoring for earlier failure detection and warning

Backup Time

300– 550 VA: 3 minutes at full load; 5 minutes typical load

 

700 VA: 2.5 minutes at full load; 5 minutes typical load

Transfer Time

4 ms typical

 

 

Table 4. Weights and Dimensions

UPS Dimensions

300 VA: 5.9 x 39.3 x 15.0 cm (2.I3 x 15.I5 x 5.9I)

(HxWxD)

550– 700 VA: 7.9 x 37.6 x 17.2 cm (3.1I x 14.I8 x 6.8I)

UPS Weight

300 VA:

3.0 kg (6.6 lb)

 

550 VA: 4.2 kg (9.2 lb)

 

700 VA:

4.3 kg (9.4 lb)

 

 

 

Table 5. Environmental and Safety

 

120V Model

230V Model

 

 

Operating Temperature

0°C to 40°C (32°F to 104°F)

Storage Temperature

-15°C to 50°C (-5°F to 122°F)

 

If the UPS is stored, the batteries should be recharged every 6 months.

 

If stored above 25°C (77°F), battery life is reduced and should be recharged more often.

Ventilation

Air around the unit must be free of dust, chemicals, or other materials

 

that corrode or contaminate.

Relative Humidity

5– 95% RH noncondensing

Audible Noise

Online: Less than 40 dBA typical at one meter

 

On Battery: Less than 45 dBA typical at one meter

Surge Energy Rating

450 joules

 

Surge Suppression

ANSI C62.41 Category A (formerly IEEE 587)

IEC 61000-4-5, Level 3

Safety Conformance

UL 1778; UL 497A;

EN 50091-1-1 and EN 60950

 

CAN/CSA C22.2, No. 107.1

 

Safety Markings

UL, cUL

NEMKO, CE

EMC (Class B)

FCC Part 15, ICES-003

EN 50091-2