Installation
STo reduce the risk of fire or electric shock, install this UPS in a temperature and
humidity controlled, indoor environment, free of conductive contaminants. Ambient temperature must not exceed 40 °C (104°F). Do not operate near water or
excessive humidity (95% max).
SWith the exception of the
SBefore maintenance or repair, all connections must be removed. Before maintenance, repair, or shipment, the unit must be completely switched off and unplugged or disconnected.
C A U T I O N
SImportant Notice The UPS ground (earth) conductor carries leakage current from the loads in addition to any leakage current generated by the UPS. This UPS generates no more than 0.5 mA of current (120V model), or 1 mA of current (230V model).
STo limit the total leakage current to 3.5 mA, the load leakage must be limited to 3 mA on the 120V model and 2.5 mA on the 230V model.
SIf you do not know the load leakage current, replace the UPS power cord (230V model only) with a power cord that uses a locking plug with a minimum rating of 10A (such as IEC 309).
SIf you do not have a matching receptacle, consult an electrician to install the proper receptacle.
SThe
Quick Startup
The PowerwareR 3110 provides protection against many power problems, including power outages. It also provides spike suppression and line noise filtering to protect your equipment.
1.On 230V models, plug the UPS power cord into the input connector on the UPS side panel.
2.Plug the equipment to be protected into the UPS output receptacles.
DO NOT protect laser printers with the UPS because of the exceptionally high power requirements of the heating elements.
2 | Powerware3110 User’s Guide S Rev B www.powerware.com |
| ® |