6.6 Float/Peak Voltage Chart

CHART RELATING THE COMPUTED FLOAT AND PEAK VOLTAGES TO THE

SELECTED NOMINAL BATTERY VOLTAGE

6.6.1. The Cell Selector becomes a Nominal Battery Voltage selector in other than the

Constant Current settings of the Voltage Mode Selector.

6.6.2. NOTE: Nominal battery voltage is referenced on the basis of 1.2V/cell for

Nickel-Cadmium batteries and 2V/cell for Lead-Acid batteries. e.g.: a 20 cell

Nickel-Cadmium battery and a 12 cell Lead-Acid battery are both considered to

be 24V batteries. Consult manufacturers specifications for optimum float and

peak voltage charge levels.

Table 1 - Constant Voltage and Peak Voltage Chart
CELL
SELECTOR FLOAT
VOLTAGE
PEAK
V
OLTAGE CELL
SELECTOR FLOAT
V
OLTAGE PEAK
V
OLTAGE
1 ----- ----- 25 29.1 30.6
2 2.3 2.5 26 30.3 31.9
3 3.5 3.7 27 31.5 33.1
4 4.7 4.9 28 32.6 34.3
5 5.8 6.1 29 33.8 35.5
6 6.7 7.4 30 35.0 36.8
7 8.2 8.6 31 36.1 38.0
8 9.3 9.8 32 37.3 39.2
9 10.5 11.0 33 38.4 40.4
10 11.7 12.3 34 39.6 41.7
11 12.8 13.5 35 40.8 42.9
12 14.0 14.7 36 41.9 44.1
13 15.1 15.9 37 43.1 45.3
14 16.3 17.2 38 44.3 46.6
15 17.5 18.4 39 45.4 47.8
16 18.6 19.6 40 46.6 49.0
17 19.8 45.3 41 47.8 50.2
18 21.0 22.1 42 48.9 51.5
19 22.1 23.3 43 50.1 52.7
20 23.3 24.5 44 51.3 53.9
21 24.5 25.7 45 52.4 55.1
22 25.6 27.0 46 53.6 56.4
23 26.8 28.2 47 54.8 57.6
24 28.0 29.4 48 55.9 58.8