Operator Manual, Supercharger 60 R3.0
Page 28 of 62
6.2 CONSTANT CURRENT CHARGE.
6.2.1. Main Charge
6.2.1.1. Program Main charging rate and time duration.
6.2.1.2. Verify that the Timer Speed is consistent with the required elapsed
time.
6.2.2. Topping Charge
6.2.2.1. Program Topping charging rate and total time of charge (Total time =
Main + Topping Times).
6.2.2.2. Start in Dual Rate
6.2.2.3. Depress the Two Rate (white) control button.
6.2.2.4. DUAL and MAIN indicators will turn on and current will rise to the set
rate in about three to five seconds.
6.2.2.5. Verify colon(:)
The colon in the digital time display will flash a the rate of one
cycle per second.
6.2.3. Single Rate Charge
6.2.3.1. For a single rate, program the current using the Topping selector
6.2.3.2. Set the required (total) time and depress the single rate (yellow) control
button.
6.2.3.3. The SING and TOP indicators will turn on and battery current will rise
to the set rate in about three to five seconds.
6.3 CONSTANT VOLTAGE CHARGE
6.3.1. Nominal Battery Voltage
6.3.1.1. Enter the nominal battery voltage using the cell selector (see chart on
page 19).
6.3.2. Maximum Charge Current
6.3.2.1. Program the maximum charge current using the Topping Current
selector.
6.3.3. Time
6.3.3.1. Program sufficient time in the Total Time selector to allow the battery
to reach the required charge level (consult battery manufacturers
specifications).
6.3.3.2. Verify that the Timer Speed is consistent with the required elapsed
time.