5 - Instructions for the Installer

The installer must read the following and provide instructions to the purchaser.

5-1 Unit controller and parameters

The Heat Pump is Equipped with 2 Control Devices:

A defrost temperature probe, located on the evaporator, starts the defrost sequence.

A thermal probe located on the exchanger ensures the cut of the heat pump when the temperature of the water reaches the temperature required.

The meaning of the code name

T1: water temperature

T2: ambient temperature

T3: exhaust temperature from compressor

T4: coil temperature in outdoor heat exchanger

TC: water temperature setting

Control Function:

1)TC can be set between 10C-35°C in cooling mode. Original TC is 18°C. When T1≤T°C -1°C, Compressor and fan motor stop; When T1≥T°C +1°C, Compressor and fan motor start.

2)TC can be set between 45°C -60°C in heating mode. Original TC is 50°C. When T1≤TC-1C, Compressor and fan motor start; When

T1≥TC+1C, Compressor and fan motor stop. When compressor is running, if T2≤12°C, the four way valve2 on; if T2≥12°C, the four way valve2 off.

5-2 Defrost operation:

1)Defrost:

The system begins to defrost if the following three terms are met in the same time:

a)T4≤-5°C lasts for a while;

b)compressor runs continuously for more than 5 minutes

c)Compressor runs accumulative total for 45 minutes

While the system begins to defrost, compressor and fan motor stop first and four way valve1 is on after 1 minute and begins to work. The compressor restarts after it has stopped for 3 minutes. If the sensor for T4 is damaged, the system begins to defrost, after the compressor has run continuously for 45

Premier Heat Pumps – Water Heater and Chiller Manual