Image 12
TWO WATER HEATERS WITH REVERSE RETURN PIPING

TWO WATER HEATERS WITH REVERSE RETURN PIPING

6CONDENSATE DRAIN, TRAP & DISPOSAL

The POWER VT PLUS water heater is designed to produce significant amounts of condensate because of its high efficiency. Condensate occurs naturally when water vapor in combustion gases is cooled below the dew point. Two 3/4” NPT drain connections are provided. A trap with three inches of standing water below the bottom of the heater (3” above the base of the I-Beam skids), and no higher than the bottom of the heater must be field installed as part of the condensate piping.

WARNING: A trap with three inches of standing water as described in these instructions must be included as part of the condensate piping system. This trap is required to keep hazardous products of combustion from continually entering the room through the condensate piping. Failure to provide this trap can cause, personal injury, exposure to hazardous materials or loss of life.

1.Installing the water heater on a 4 inch to 6 inch housekeeping pad is recommended to ensure proper condensate drainage.

2.Attach a 3/4” CPVC Coupling and Tee to the economizer condensate drain, then use 3/4” CPVC pipe to plumb from the heater condensate outlet to economizer Tee, to a 3” CPVC trap and on to a suitable floor drain or collection system. Each condensing appliance must drain separately. Do not combine condensate drains from multiple condensing appliances into a single drain pipe.

3.Each condensate drain must contain a trap or siphon/pigtail to provide at least 3 inches of standing water, to prevent flue gas flow through the condensate piping. To construct the trap, connect to the 3/4” condensate drain, route the piping downward until the standing water in the trap is not higher than the bottom of the water heater.

4.Install the condensate plumbing as shown in the following diagram.

5.All condensate plumbing must be protected from freezing. Do not locate the condensate piping such that an ice dam of frozen condensate can block the outlet.