PVI Industries 150, 180 manual 11.8LED Display Alarm Messages, Cause, Results Of Alarm Condition

Models: 150 180

1 44
Download 44 pages 43.39 Kb
Page 25
Image 25
11.8LED Display Alarm Messages

11.8LED Display Alarm Messages

Alarm messages are displayed in the upper LED readout and alternate with the default display. An alarm LED ICON is also illuminated. (See TempTrac User Manual PV500-40 for full description.)

ALARM

CAUSE

RESULTS OF ALARM CONDITION

MESSAGE

 

 

 

 

Inlet temperature sensor is not

“P1”

TP1 probe failure

connected or is reading incorrectly. Call

for heat and burner modulation output

 

 

 

 

signal will revert to low fire.

 

 

 

 

 

Temperature sensor is not connected

“P2”

TP2 probe failure

or is reading incorrectly. Freeze

 

 

protection is disabled.

 

 

Temperature sensor is not connected

“P3”

TP3 probe failure

or is reading incorrectly or flue gas

temperature protection is disabled (if

 

 

 

 

used).

“HA”

High temperature limit

Buzzer sounds, operation continues

setpoint exceeded

 

 

“LA”

Low temperature alarm

Buzzer sounds, operation continues

 

 

 

 

Digital input 3 is activated

 

 

for one or more of the

 

HP

following:

Unit de-energized after timer delay

Flame failure or any control

 

component failure, if

 

 

equipped with alarm on any

 

 

failure option

 

LP

Digital input 2 is activated

Unit de-energized after timer delay

 

 

 

Mn1

Maintenance alarm for

Buzzer sounds, operation continues

output 1

 

 

Mn2

Maintenance alarm for

Buzzer sounds, operation continues

output 2

 

 

Mn3

Maintenance alarm for

Buzzer sounds, operation continues

output 3

 

 

“rtc”

The real time clock has lost

Energy saving function disabled

its setting

 

 

RECOMMENDED

ACTION

Check wiring and sensor

Terminals 14 & 17

Check wiring and sensor

Terminals 15 & 17

Check wiring and sensor

Terminals 16 & 17

Manual reset required

Manually reset required

Manually reset required

Check wiring and sensor

Check wiring and sensor

Check wiring and sensor

Reprogram clock

25

PV500-46U 06/12

Page 25
Image 25