4300 ACT Wood Stove Series

FLOOR PROTECTION

FLOOR PROTECTION: Floor protector must be noncombustible material, extending beneath heater and to the front/sides/rear as indicated. The floor must be non-combustible or otherwise adequately protected from radiant heat given off by the unit and from sparks and falling embers. A layer of thin brick or ceramic tile over a combustible floor is not sufficient. A listed hearth pad that has a “k” value of .84 or lower meets this requirement.

In USA installations, it is necessary to install a floor protector of 1/2" thick metal clad millboard (“k” value = .84) or equivalent at least 16" in front of glass door and 8" to both sides of the fuel loading door. Open the door and measure 8” from the side edge of the opening in the face of the stove. See *exception below.

See Alternate Materials Worksheet on Page 9 to determine if alternate floor protection materials are acceptable.

In Canada, similar floor protection must be provided 18" (457mm) in front and 8" (203mm) from the sides and rear of the stove. See *exception below.

*EXCEPTION: Non-combustile floor protection must extend beneath the flue pipe when installed with horizontal venting and extend 2” (51mm) beyond each side.

NOTE: Drawings are for illustration purposes only and are not to scale.

USA 4300 Millennium

USA 4300 Step Top Uni-Body

Canada - Both Models

 

 

 

 

203mm (8")

3-1/4"

 

2-3/4"

 

 

 

 

203mm

203mm

 

 

 

 

4-3/4"

 

 

5-1/4"

(8")

(8")

 

 

 

40-1/2"

 

 

 

40-3/4"

 

 

Fuel loading door

 

 

minimum

 

 

 

minimum

Fuel loading door

 

 

 

 

 

 

 

16" from glass

8"

 

8"

457mm (18")

 

 

 

 

 

 

16" from glass

 

 

 

USA

 

 

CANADA

 

 

USA

 

31-5/8" minimum

 

 

31-5/8" minimum

Millennium

Step Top Uni-body

 

 

 

 

1054mm (41-1/2")

1080mm (42-1/2)

 

 

 

 

minimum

minimum

Millennium

1287mm (50-3/4") minimum

Step Top 1288mm (50-1/2") minimum

USA -4300 Millinneum

USA 4300 Uni-Body Step Top

Horizontal Venting

 

Both Models

56-5/8"

48-1/2"

optional

coverage

-5/8"

 

31

56-5/8"

optionalcoverage

30.0"

 

coverage

optional

optional

"

coverage

 

-5/8

 

 

31

 

48-1/2"

30.0"

optionalcoverage

USA

30.0"

-3/4" 40

16" required

coverage

.0" 26

optionalcoverage

USA

30.0"

 

"

2

-1/

 

40

 

16" required

coverage

.0" 26

Must extend 2" (51mm) beyond each

side of pipe (shaded area)

USA - Required

Canada - Recommended

Page 8

250-7061C December 10, 2004

Page 8
Image 8