Raypak 0180B manual Safe Shut-Downtests Limit Action, Flame Failure, Inspection Procedures Burners

Models: 0042B 0180B 0066B

1 39
Download 39 pages 210 b
Page 28
Image 28
SAFE SHUT-DOWN TESTS

SAFE SHUT-DOWN TESTS

LIMIT ACTION

With the burner operating, lower the high limit setting to simulate an overheated boiler. Normal shut- down should occur. Restore the normal limit setting, and the burner should restart.

FLAME FAILURE

With burner operating, close the manual fuel valves to simulate a flame failure. System should lock out after safety switch timing (15 seconds). After the safety switch has cooled, open the manual valves (relight standing pilots) and reset the safety switch; the burner should restart.

INSPECTION PROCEDURES

BURNERS

Clean main burners and air louvers of dust, lint and debris. Keep boiler area clear and free from combustibles and flammable liquids. Do not obstruct the flow of combustion and ventilation air. Make visual check of burner and pilot flame. Yellow flame indicates clogging of air openings. Lifting or blowing flame indicates high gas pressure. Low flame indicates low gas pressure.

Fig. #8964

PILOT BURNER FLAME (STANDING PILOT UNITS)

INSPECTIONSCHEDULE

To be performed the first and third month after initial start up and then on an annual basis. If problems are found, refer to Troubleshooting Guide for additional direc- tions.

1.Remove top of boiler and inspect heat exchanger for soot and examine venting system.

2.Remove rear header and inspect for scale depos- its.

*3. Inspect pilot and main burner flame and firing rate.

*4. Inspect and operate all controls and gas valve.

*5. Visually inspect system for water leaks.

*6. Inspect oil pump motor and bearing assembly, if oil cups are provided.

7.Check flow switch paddle.

8.Clean room air intake openings to ensure adequate flow of combustion and ventilation air.

9.Keep boiler area clear and free from combustible materials, gasoline, and other flammable vapors and liquids.

*Should be checked monthly. (Takes approximately 15 minutes).

Fig. #8144

MAIN BURNER FLAME

NOTE: Modulating burner flame varies in height from approximately 1/4" at low fire to approximately 4" in high fire.

28

Page 28
Image 28
Raypak 0180B, 0066B Safe Shut-Downtests Limit Action, Flame Failure, Inspection Procedures Burners, Inspectionschedule