For safe, efficient operation, the vent damper and all flue-product-carrying areas of the appliance must be checked annually, with particular attention given to deterioration from corrosion or other sources.

Check vent damper operation as follows:

1. When the boiler is off, check that the vent damper position indicator points to the closed position, below.

DAMPERPOSITION

DAMPERPOSITION

INDICATOR

INDICATOR

NOTE: To place vent damper in the open position to allow burner operation:

Turn the power off. Turn the damper blade to fully open position (arrow facing same direction as vent pipe). Turn power on.

DAMPER OPEN

DAMPER CLOSED

Fig. # 8181.0

VENT DAMPER POSITION INDICATOR

2.Turn the thermostat or controller up to call for heat and check that the vent damper indicator points to the open position, above.

3.Turn the thermostat or controller down again and check that the vent damper position indicator returns to the closed position.

THE VENT DAMPER MUST BE INSPECTED AT LEAST ONCE A YEAR BY A TRAINED, EXPERIENCED

SERVICE TECHNICIAN. THE NAME OF THE PERSON WHO ORIGINALLY INSTALLED YOUR VENT DAMPER IS SHOWN ON THE INSTALLATION LABEL. DAMPER MUST BE IN OPEN POSITION WHEN BOILER MAIN BURNERS ARE OPERATING.

FLAIR DAMPER

 

SYSTEM SCHEMATIC

LEGEND

LADDER DIAGRAM

 

 

R

 

 

 

 

R2

SS2

ES

 

SC

 

SS 1

 

 

R1

 

 

 

 

 

JUMPER

 

 

M

 

 

 

1

2

3

4

 

GV

HL

 

 

 

 

 

TH

 

24 VAC

 

 

 

 

TR

 

 

 

120 VAC

 

 

L

60Hz

L

 

 

 

1

2

 

 

M - Damper motor R - Relay

ES - End switch

SS1 - N/C Safety switch SS2 - N/O Safety switch contacts

TR - Transformer 120/24V HL - High limit

GV - 24V gas valve

TH - Thermostat, heating, low voltage

J - Jumper

Note: Circuit shown with damper in closed position, no call for heat.

Fig. #9002

24

V

AC

 

TH

R

 

 

 

 

 

2

 

 

 

4

 

 

GV

 

 

SS

3

J

HL

 

1

ES

 

 

 

 

SS

R

 

 

2

2

SC

 

 

 

M

 

 

R 1

 

 

 

Fig. #9003

9

Page 9