5. SERVICING UNIT

TROUBLE SHOOTING GUIDE

 

 

 

 

PROBLEM

POSSIBLE CAUSE

SUGGESTED SOLUTION

1.

On-Off switch energized. Unit

1a. No power to heater

a.

Cycle the Power Switch off then on.

 

does not operate.

 

 

-Check circuit breaker and electrical

 

 

 

 

disconnect.

 

 

 

 

-Check for reversed polarity and im-

 

 

 

 

proper ground.

 

 

 

 

-Check dishwasher vent interlock, if

 

 

 

 

applicable.

 

 

1b. Defective transformer

b.

Check secondary voltage.

 

 

 

 

If no 24 volts, replace transformer.

 

 

 

 

 

 

2.

Pump/Blower NOT running.

2a. Loose wire(s)

2a.

Check wiring connection(s)

 

 

 

 

-Check pump amperage. If pump

 

 

 

 

does not draw 0.67-0.78 amps, re-

 

 

 

 

move and inspect impeller.

 

 

2b. Defective pump

2b.

Replace cartridge or entire pump as

 

 

 

 

needed.

 

 

2c. Defective blower.

2c.

Clean and inspect blower wheel.

 

 

 

 

-Check operation.

 

 

 

 

-Replace blower if needed

 

 

 

 

 

 

3.

Unit energized, pump and

3a. Limit control (operating limit)

3a.

If Red LED on circuit board is ON,

 

blower running, but burner is

or sensor may be defective.

 

check for a loose sensor connection

 

NOT on.

 

 

or defective sensor. Sensor resis-

 

 

 

 

tance readings:

 

 

 

 

60°F = 45,500± 2300 ohms

 

 

 

 

80°F = 28,000± 1300 ohms

 

 

 

 

If Yellow LED is ON , water tempera-

 

 

 

 

ture is above set point. When either

 

 

 

 

Red or Yellow LED is ON, heater will

 

 

 

 

be shut down. Check 24V, power at

 

 

 

 

OUT and COMM terminals. If no 24V

 

 

 

 

is present when Red or Yellow LED is

 

 

 

 

not ON, replace control board.

3b. Blocked vent or defective air vent switch.

3b. Excessive vent length or resistance or blocked vent will open the air vent switch. Remove blockage. If switch stays open, replace air vent switch.

3c. Tripped or defective manual

3c. Depress the Manual Reset High Limit

reset limit.

switch.

 

-Ensure Operating Limit setting is

 

185°F or less.

 

-Perform Pump Check Procedure.

 

(High Limit trips may be due to a

 

damaged pump).

 

-Perform Operating Limit Check

 

Procedure.

 

-If High Limit will not reset, replace

 

High Limit