Raypak RFSDV34RFNAU manual Troubleshooting the Gas Control System, Control Local Path, On Path

Models: RFSDV34RFPAU RFSDV34RFNAU

1 27
Download 27 pages 4.22 Kb
Page 20
Image 20
Troubleshooting the Gas Control System

Troubleshooting the Gas Control System

Comfort Valve System Control Sequence of Operation with Remote

Control

Local Path

Set manual switch to local or remote

Light pilot burner

Did the LED stop

blinking?

Release pilotstat

knob

Turn pilotstat

knob from PILOT

to ON

Five minute wait period

Review LED

failure analysis

Cycle switch once and leave in remote. Press any key on the Remote Control for recognition operation.

If manual switch is set to LOCAL, did main burner light and fan turn on?

Yes

Turn pilotstat knob to

PILOT to turn off

main burner

Turn pilotstat knob to

OFF to turn valve

completely off.

Choose Manual or Remote path. Set switch to manual or remote.

Move switch from manual to remote.

Press any key on the

remote control.

Move switch back to

On Path

If the manual switch

is set to remote, press the mode button to display ON. Does the remote control the main burner and fan?

Yes

Does remote

control change levels of flame height, fan speed?

Yes

Set levels of flame height and fan to “0” to shut off main burner and fan

Turn pilotstat knob

to OFF to turn

valve completely

off

Move switch from manual to remote. Press any key on remote control

No

Auto Path

If the manual switch

is set to remote, press the mode button to display AUTO. Does the remote control display the room and temperature settings?

If the setting is

above room

temperature on

the remote control

does the main

valve and fan turn

on?

If the setting is

below room

temperature on

the remote

control, does the main valve and fan turn off?

Turn pilotstat knob

to OFF to turn

valve completely

off.

Move switch from

local to remote.

Press any key on

remote control

within 30 seconds

No

No

Page 20 of 27

Page 20
Image 20
Raypak RFSDV34RFNAU manual Troubleshooting the Gas Control System, Control Local Path, On Path, Auto Path, Page 20 of