INSTALLATION

OPTIONAL WALL

OPTIONAL REMOTE

THERMOSTAT

CONTROL

FINAL CHECK

Before leaving this unit with the customer, the installer must ensure that the appliance is firing

A wall thermostat may be installed if desired. Connect the wires as per the wiring diagrams. Note that the wires are connected to the "TH" on the gas valve. Use table below to determine the maximum wire length:

Note: Preferable if the thermostat is installed on an interior wall.

Regency offers an optional programmable thermostat but any 250-750 millivolt rated non- anticipator type thermostat that is CSA, ULC or UL approved may be used.

CAUTION

Do not connect the millivolt

wall thermostat wires

to the 240 V wires.

Thermostat Wire Table

Recommended Maximum Lead Length

(Two-Wire) When Using Wall

Thermostat (CP-2 System)

Wire Size

Max. Length

14 GA.

15.24

m

16 GA.

9.75

m

18 GA.

6.10

m

20 GA.

3.66

m

22 GA.

2.71

m

Use the Regency Remote Control Kit approved for this unit. Use of other systems may void your warranty.

The remote control kit comes with a hand held transmitter, a receiver and a wall mounting plate.

1)Choose a convenient location on the wall to install the receiver and the receptacle box (protection from extreme heat is very important). Run wires from the fireplace to that location, use Thermostat Wire Table.

2)Connect the wires as per the wiring diagram above.

CAUTION

Do not connect the millivolt

remote control wires to

the 240V wires.

3)Install 3 AAA alkaline batteries in transmitter and 4 AA alkaline batteries in the receiver. Install the receiver and its cover in the wall. Switch the remote receiver to "remote" mode. The remote control is now ready for operation.

correctly. This includes:

1)Clocking the appliance to ensure the cor- rect firing rate (rate noted on label) at 15 minutes.

2)If required, adjusting the primary air to ensure that the flame does not carbon. First allow the unit to burn for 15 min. to stabilize.

3)Check for proper draft.

CAUTION

Any alteration to the product that causes sooting or carboning that results in damage to the exterior facia is not the responsibility of the manufacturer.

12

Regency F38-2 Freestanding Gas Stove

Page 12
Image 12
Regency F38-NG2, F38-LPG2 installation manual Final Check, 14 GA 15.24 16 GA 18 GA 20 GA 22 GA