Gas Fireplaces

P121-P131 Gas Fireplace

Venting Arrangements - Horizontal

Terminations

This diagram shows allowable venting confi gurations using one 45°.

Note: Must use optional flue adapter (Part # 770-994) when using Rigid Pipe.

Maintain clearances to combustibles.

Horizontal vent must be supported every 3 feet.

Firestops are required at each fl oor level and whenever passing through a wall.

A vent guard should be used whenever the termination is lower than the specifi ed minimum or as per local codes.

Note: FPI Direct Vent System (Flex) is only approved for horizontal terminations.

74

Gas Fireplaces

Horizontal Venting with One (1) 90° Elbow

Two 45° elbows = One 90° elbow

Option

V

H

Maximum total pipe: length, of

 

 

 

all sections, must not exceed

A)

1’ Min.

3’ Max.

37 feet.

 

 

 

B)

2’ Min.

6’ Max.

Total horizontal sections must

 

 

 

not exceed 17 feet.

C)

3’ Min.

9’ Max.

Minimum of 1 foot between

 

 

 

D)

4’ Min.

12’ Max.

90° elbows is required.

E)

5’ Min.

15’ Max.

 

 

 

 

 

F)

6’ Min.

17’ Max.

 

June 2007 Regency Product Specifications Book

Page 6
Image 6
Regency P121/P131-LP2, P121/P131-NG2 Venting Arrangements Horizontal Terminations, Horizontal Venting with One 1 90 Elbow