Gas Fireplaces
Framing and Finishing
1)Determine the total thickness of facing material (e.g. drywall plus ceramic tiles) to allow the fi nished surface to be fl ush with the front of the unit. Total facing thickness can vary from 1/2” (13mm) to
2)Frame in the enclosure for the unit with framing material.
3)For exterior walls, insulate the enclosure to the same degree as the rest of the house, apply vapor barrier and drywall, as per local installation codes. (Do not insulate the fireplace itself.)
4)The top of the unit must not be closer than 36” (990mm) to the ceiling.
5)Combustible material may be brought up to the top and sides of the unit and be covered with ceramic tiles, bricks, rock or other suitable combustible finishing materials.
Note: The unit does not have to be completely enclosed in a chase. The clearance on top of the unit is 0” to the standoffs so combustible building materials can be laid directly on top of the standoffs. You must maintain proper clearances from the vent to combustible materials (See Below).
6)Use metal studs for framing where the minimum clearance from the vent to combustible material cannot be maintained.
Clearance Requirements
Gas Fireplaces
Parallel Wall Clearances
Unless otherwise stated the clearances listed below are Minimum distances to combustible materials. Unit pictured is a P131
Parallel Wall Clearances | P121(LC/RC)/131 |
Min distance from glass to a parallel wall | 36” (914mm) |
36"min. | 36"min. |
(914mm) | (914mm) |
36"min. (914mm) |
Vent Clearances | Clearance Dimension |
Horizontal - Top | |
Horizontal - Side | |
Horizontal - Bottom | |
Vertical |
D
C
A
F
B
B
WARNING
Failure to maintain required clearances is a major cause of chimney related fires. Installation of this fireplace must comply with these clearances.
Combustible Mantels
Because of the extreme heat this fireplace emits, the mantel clearances are critical. Combustible mantel clearances from top of the louvers are shown in the diagram below. Mantel may be installed anywhere in the shaded area or higher.
Mantel Clearances
12 | 10 | 8 | 6 | 4 | 2 | 0 | ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| E |
|
|
|
|
|
|
Clearance: | Dimension |
|
| Measured From: |
A: Mantel Height | 3” (76mm) | Minimum (Additional on this page) |
Note: Ifthefireplaceisinstalled without the 3” Extension Trim, the facing material must be non combustible up to 8” above the unit.
0
| 12" (305mm) | Drywall | |
|
| ||
|
|
| Header |
|
|
| Standoff |
B |
| 3 ½" (89mm) |
|
|
|
| |
|
| C | 3” Extension Trim |
|
|
| |
| A | Top of |
|
| Unit |
| |
|
|
|
B: Sidewall | 0” (0mm) |
| Side of installed front |
| 3” (76mm) |
| On |
|
|
| 3” clearance opposite vent. |
C: Ceiling | 36” (914mm) |
| Top of installed unit |
D: Mantel Depth | 12” (305mm) |
| Maximum (Additional on this page) |
E: Alcove Width | See Parallel Wall Clearances. | ||
F: Alcove Depth | 36” (914mm) |
| Front to back wall (Maximum) |
| |||
|
|
|
|
Top of Hearth must not be higher than the base of the fi rebox.
70
|
|
| Side View | |
|
|
|
|
|
Mantel Clearances | A | B |
| C |
Front | 36” (914mm) | 7” (178mm) |
| 3” (76mm) |
|
|
|
|
|
Note: If desired a
Note: Ensure the paint that is used on the mantel and the facing is “heat resistant” or the paint may discolour.