Generator Installations
NOTICE The figures below demonstrate the minimum installation distances allowed to structures and items shown in legend.
AAA
Exhaust
Direction
5 ft (1.5 m)
B
| 18 in. (45.7 cm) min. | |
5 ft (1.5 m) |
| 5 ft (1.5 m) |
Standby |
| Standby |
|
| |
| 5 ft (1.5 m) | Exhaust |
|
| |
|
| Direction |
B
A |
|
| A | |
18 in. | 18 in. (45.7 cm) min. | 5 ft (1.5 m) | ||
(45.7 cm) min. | ||||
|
|
| ||
|
| Standby |
| |
Standby |
|
|
| |
Exhaust | 5 ft (1.5 m) | Exhaust |
| |
Direction |
| |||
| B | Direction |
| |
|
|
| ||
5 ft (1.5 m) |
|
|
| |
A | A |
| B | |
|
|
|
Legend for Generator Locations to reduce the risk of fire.
AStandby weatherproof enclosure must be at least 5 ft (1.5 m) from windows, doors, any wall opening, shrubs or vegetation over 12 inches (30.5 cm) in height.
BExhaust outlet side of weatherproof enclosure must have at least 5 ft (1.5 m) minimum clearance from any structure, shrubs, trees or any kind of vegetation.
CStandby weatherproof enclosure must have a minimum of 5 feet (1.5 m) overhead clearance from any structure, overhang or trees.
NOTICE DO NOT place weatherproof enclosure under a deck or other type of covered structure that may confine airflow.
15