Rinnai ES38 Flue Terminal Clearances, Description, Canadian Installations, US Installations

Models: ES38

1 44
Download 44 pages 45.27 Kb
Page 17
Image 17
Flue Terminal Clearances

Flue Terminal Clearances

Ref

Description

Canadian Installations

US Installations

 

 

 

 

 

Clearance above grade, veranda,

 

 

A

porch, deck, or balcony. (Take into

12 inches (30 cm)

12 inches (30 cm)

 

account the anticipated snow line)

 

 

 

 

 

 

 

 

6 inches (15 cm) for

6 inches (15 cm) for

 

 

appliances < 10,000 BTUh;

appliances < 10,000 BTUh;

B

Clearance to window or door that may

12 inches (30 cm) for

9 inches (23 cm) for

appliances > 10,000 BTUh

appliances > 10,000 BTUh

be opened

 

and < 100,000 BTUh,

and < 50,000 BTUh,

 

 

 

 

36 inches (91 cm) for

12 inches (30 cm) for

 

 

appliances > 100,000 BTUh

appliances > 50,000 BTUh

C

Clearance to permanently closed

*

*

 

 

 

 

 

Vertical clearance to ventilated soffit,

 

 

D

located above the terminal within a

*

*

horizontal distance of 2 feet (61 cm)

 

 

 

 

from the center line of the terminal

 

 

 

 

 

 

E

Clearance to unventilated soffit

*

*

 

 

 

 

F

Clearance to outside corner

*

*

 

 

 

 

G

Clearance to inside corner

20 inches (50 cm)

20 inches (50 cm)

 

 

 

 

 

Clearance to each side of center line

3 feet (91 cm) within a height

 

H

extended above meter/regulator

15 feet (4.5 m) above the

*

 

assembly

meter/regulator assembly

 

 

 

 

 

I

Clearance to service regulator vent

3 feet (91 cm)

*

 

 

 

 

 

 

6 inches (15 cm) for

6 inches (15 cm) for

 

 

appliances < 10,000 BTUh;

appliances < 10,000 BTUh;

 

Clearance to nonmechanical air supply

12 inches (30 cm) for

9 inches (23 cm) for

J

inlet to building or the combustion air

appliances > 10,000 BTUh

appliances > 10,000 BTUh

 

inlet to any other appliance

and < 100,000 BTUh,

and < 50,000 BTUh,

 

 

36 inches (91 cm) for

12 inches (30 cm) for

 

 

appliances > 100,000 BTUh

appliances > 50,000 BTUh

K

Clearance to a mechanical air supply

6 feet (1.83 m)

3 feet (91 cm) above if within

inlet

10 feet (3 m) horizontally

 

 

 

 

 

 

L

Clearance above paved sidewalk or

7 feet (2.13 m) 1

*

paved driveway located on public

 

 

 

 

 

 

 

 

Clearance under veranda, porch, deck,

12 inches (30 cm) to non-

12 inches (30 cm) to non-

M

flammables 2

flammables 2

or balcony

24 inches (60 cm) to

24 inches (60 cm) to

 

 

 

flammables 2

flammables 2

 

 

 

 

1A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.

2Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor. For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, clearances are in accordance with local

installation codes and the requirements of the gas supplier.

Rinnai Corporation ES38 Manual

17

Page 17
Image 17
Rinnai ES38 installation manual Flue Terminal Clearances, Description, Canadian Installations, US Installations