Maximum Vent Length
1.Determine the number of 90 degree elbows in the vent system. Two 45 degree elbows count as one 90 degree elbow.
2.Refer to the table to find the maximum vent length based on the number of elbows.
3.Follow the applicable note.
Example: If you have one elbow then your maximum vent length is 35 feet (10.7 m). If your actual length is greater than 15 ft (4.6 m) then move dip switch no. 1 (SW1) to OFF.
Number of 90° Elbows
0 | 1 | 2 | 3 | 4 | 5 | 6 |
|
|
|
|
|
|
|
41 ft 1 | 35 ft 2 | 29 ft 3 | 23 ft 4 | 17 ft 4 | 11 ft 4 | 5 ft 4 |
(12.5 m) | (10.7 m) | (8.8 m) | (7.0 m) | (5.2 m) | (3.4 m) | (1.5 m) |
|
|
|
|
|
|
|
1If the length is greater than 21 ft (6.4 m) then move
dip switch no. 1 (SW1) to OFF. | Notes 1234 |
|
2If the length is greater than 15 ft (4.6 m) then move dip switch no. 1 (SW1) to OFF.
3If the length is greater than 9 ft (2.7 m) then move dip switch no. 1 (SW1) to OFF.
4Move dip switch no. 1 (SW1) to OFF.