Roberts Gorden 200 Servicing Instructions, Burner Maintenance, Heat Exchanger Maintenance

Models: 175 225 300 250 400 150 350 200

1 62
Download 62 pages 5.65 Kb
Page 40
Image 40
SECTION 13: SERVICING

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL

SECTION 13: SERVICING

DANGER

 

WARNING

 

Electrical Shock Hazard

Explosion Hazard

Burn Hazard

Cut/Pinch Hazard

Disconnect electric

Turn off gas supply to

Allow heater to cool

Wear protective gear

heater before service.

before service.

during installation,

before service.

 

 

operation and service.

Heater must be

 

Tubing may still be hot

 

 

connected to a properly

 

after operation.

Edges are sharp.

grounded electrical

 

 

 

source.

 

 

 

Failure to follow these instructions can result in death, electric shock, injury or property damage.

13.1 Servicing Instructions

After start-up, the heater will require maintenance to be carried out, at a minimum, annually. If the heater is used in a dirty or dusty area, more frequent maintenance may be required.

IMPORTANT: After any maintenance or repair work, always test fire the heater in accordance with the start-up instructions on Page 27, Section 11 through Page 30, Section 11.3.1 to ensure all safety systems are in working order before leaving the heater to operate. Minor faults may be traced by using the troubleshooting charts on Page 35, Section 14 through Page 39, Section 14.5.

IMPORTANT: Check all gas pipes and pipe joints to ensure there are no cracks or gas leaks. Any cracks in the pipes or pipe joints must be repaired.

IMPORTANT: Inspect all suspended components and hardware. Ensure that they are in good condition, properly tightened, and corrosion free.

13.2 Burner Maintenance

1.Open the door and remove the burner compart- ment cover. See Page 41, Section 15.2.

2.Clean any deposits from the main burner which may have formed in the injectors or venturi of the burner. See Page 41, Section 15.2.

3.Remove the ignition electrode and flame probe. Check condition of ignition electrode and flame probe. Clean off any deposits which may have been formed, check condition of ceramic

insulators. Replace as necessary. See Page 42, Section 15.3.

13.3 Fan/Motor Assembly Maintenance

The main fan bearings are permanently sealed and do not need lubrication. Before cleaning, turn off gas and electrical supply. Remove the fan and use a small brush or duster to clean the fan blades from each side. Replace fan when done.

13.4 Heat Exchanger Maintenance

The heat exchanger will remain clean unless a problem has developed with combustion. Inspect the heat exchanger. Look for signs of overheating at the front tubes which may indicate burner over firing or persistently low air flows.

13.5 Gas Valve Maintenance

No regular maintenance is required on this device. To change gas control valves, See Page 40, Section 15.1.

Do not repair or disassemble gas valve.

Replace faulty gas valves with genuine replacement parts sold and supplied by Roberts-Gordon LLC.

13.6 Flue Blower

The flue blower should not require maintenance. However, if the air pressure switch is causing burner lockout, then remove the flue blower from the vent box by unscrewing the three screws at the mounting plate. Remove the four screws attaching the mounting plate to the fan inlet (See Page 44, Section 15.6). Ensure that the fan is free to run and that the fan wheel is clean.

32 of 51

Page 40
Image 40
Roberts Gorden 200, 350 Servicing Instructions, Burner Maintenance, 13.3 Fan/Motor Assembly Maintenance, Flue Blower