SECTION 6: HEATER INSTALLATION 6.1 General

UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL

SECTION 6: HEATER INSTALLATION 6.1 General

Heaters are designed for installation above 6'

(1.8 m). These heaters must be installed within the heated space. Duct delivery systems are not permitted with axial fan units. When handling or supporting the heater from below, ensure that the weight is taken at the support points.

The gas or electrical supply lines must not be used to support the heater.

Do not locate the gas or electrical supply lines directly over the path of the flue products from the heater.

The heater must be installed in a location that is readily accessible for servicing.

The heater must be installed in accordance with clearances to combustibles as indicated on the wall tag and in this manual.

6.2 Suspension

6.2 Suspension WARNING

Crush Hazard

Use 3/8" threaded rod minimum.

Failure to follow these instructions can result in death, injury or property damage.

Four suspension points (3/8" nuts) are located on the top of the heater. Drop rods must be 3/8" diameter mild steel minimum.

When handling or supporting the heater from below, ensure that the weight is taken at the support points. For typical suspension, See Page 10, Figure 5.

Figure 5: Suspension Methods