SECTION 11: OPERATION AND MAINTENANCE
Figure 14: Gas Valve for Models UHA[X][S] 150 - 400
END VIEW | TOP VIEW |
|
| Regulator |
|
| ½PSI |
|
| C |
|
| IN |
|
|
| ON |
Gas Inlet | OFF | Outlet |
| ||
| Pressure | |
|
| |
| Description | Part Number |
| Gas Valve 150 - 250 NG | 90032505 |
| Gas Valve 150 - 250 LP | 90032506 |
| Gas Valve 300 - 400 NG | 90032520 |
Inlet Pressure | Gas Valve 300 - 400 LP | 90032521 |
11.2.2
1. Remove the plug in the outlet (burner) pressure test point and connect a pressure tap and a manometer.
2.With the burner firing, measure the pressure on the manometer. To adjust the burner pressure, remove the regulator cover from the valve and turn the regulator adjustment screw to set the required burner pressure as stated in the Technical Data Table for the correct gas and model on Page 49, Section 16.3.
NOTE: If the correct burner pressure cannot be reached, then check the inlet pressure to the valve with the burner firing. See Technical Data Table on Page 49, Section 16.3 for inlet pressure requirement.
Do not continue to adjust the regulator if the pressure is not changing.
If the inlet pressure is too low to allow correct burner pressure setting, then the gas inlet pressure must be corrected before completing the
Check Gas Rate
1.After burner pressure adjustment, allow the heater to operate for at least 15 minutes and then
2.Check gas flow rate at gas meter.
3.Turn off heater and electrical supply.
4.Remove the manometer and refit all covers to the valve and tighten the screw of the outlet pressure tap.
11.2.3 Pressure Switch
The pressure switch is factory
11.2.4 Turning Off the Heater
Set the thermostat to the "OFF" position or lowest setting and the main burner will stop.
The fan will continue to run until it is stopped automatically by the fan thermostat.
Do not use a disconnect switch for control of heater. Disconnect switch will turn off the fan. Heat exchanger could be damaged. Warranty will not cover damage to the heat exchanger if operated improperly. Only use the disconnect switch for turning off heater for service or during