Roberts Gorden CRV-Series service manual Typical Suspension Details, Description

Models: CRV-Series

1 40
Download 40 pages 52.2 Kb
Page 14
Image 14
HEATER INSTALLATION

ROBERTS GORDON® CRV-SE RI ES SUBMI TT AL SHE ET

HEATER INSTALLATION

Critical Hanger Placement

Typical Suspension Details

Beam Clamp

Anchor

Screw Hook (3/8") Typical Suspension Details

 

 

Chain size

 

Rod (3/8")

3/16" minimum

 

 

24" min.

 

 

(61 cm)

"X" (see table)

 

 

Turnbuckle

 

 

“S” Hook

Locknut Description(Typical)

Concrete Beam

Wood Beam

Locknut

Washers Manual background

Manual backgroundManual background 7'6" (2.3 m) Manual backgroundManual background

 

 

 

Turnbuckle

 

 

 

 

Hanger

 

 

 

 

Reflector

 

 

Side View

Towards Pump

Front View

Description

Part Number

Run Length

Typical Expansion

Minimum “X” Length

Turnbuckle

91903201

50' (15 m)

±1" (3 cm)

12" (30 cm)

S-Hook

91907302

100' (31 m)

±2" (5 cm)

24" (61 cm)

Tube/Reflector Hanger

03090100

150' (46 m)

±3" (8 cm)

36" (91 cm)

 

 

200' (61 m)

±4" (10 cm)

46" (122 cm)

 

 

250' (76 m)

±5" (13 cm)

57" (145 cm)

© 2004 Roberts-GordonBEFORE IN STALLATI ON AND OPER ATI ON OF HEATI NG EQUIPMENT, READ AND U NDERSTAND THE INSTALLATION, OPERATIO N AND SERVICE MANUAL .

APPLICATION S, ENGI NEERING AND DETAI LED GUID ANCE ON SYSTEMS DESIGN, INSTALLATI ON AND PRODUCT PERFORMANCE IS AVAI LABLE UPON REQUEST. ROBERTS GORDON® PRODUCTS ARE TO BE INSTALLED ONLY IN ACCORDANCE WI TH LOCAL LAWS, CODES AND REGULATIONS, AND ONLY BY A CONTRACTOR QUALI FIED I N THE I NSTALLATION AND SERVICE OF GAS-FIRED HEATING EQUI PMENT.

Page 14
Image 14
Roberts Gorden CRV-Series Typical Suspension Details, HEATER INSTALLATION Critical Hanger Placement, Description