SECTION 16: REMOVAL AND REPLACEMENT PARTS
Attach this information to the wall near the ROBERTS GORDON® heater
®
Read the Installation, Commissioning, Operation and Service Manual thoroughly before installation, operation or service.
OPERATING INSTRUCTIONS | WARNING |
| |
|
|
1.STOP! Read all safety instructions on this information sheet.
2.Open the manual gas valve in the heater supply line.
3.Turn on electric power to the heater.
4.Set the thermostat to desired setting (above ambient temperature). The automatic starting sequence begins.
NOTE: Following long shutdown periods, the burner control may go to to 'LOCKOUT' during the start sequence. Push the reset button to recommence firing. Contact service department if 'LOCKOUT' continues (see manual for details).
TO TURN OFF THE HEATER
1. Turn the thermostat/time switch to 'OFF'. The burner will turn 'OFF' |
| Fire Hazard | |||
immediately, but fans will continue to cool heat exchanger until the fan |
|
| |||
thermostat switches off. |
| Some objects can catch fire or explode when placed | |||
|
|
|
| ||
IF THE HEATER WILL NOT OPERATE, TO ENSURE YOUR SAFETY, | close to heater. |
| |||
|
| ||||
FOLLOW THESE INSTRUCTIONS TO SHUT DOWN YOUR HEATER | Keep all flammable objects, liquids and vapors the | ||||
|
|
|
| ||
1. Set the thermostat to off or the lowest setting. | required clearances to combustibles away from heater. | ||||
|
| ||||
2. Turn off electric power to the heater. | Failure to follow these instructions can result in death, | ||||
3. Turn off the manual gas valve in the heater supply line. | |||||
4. Call your registered installer/contractor qualified in the installation | injury or property damage. | ||||
and service of |
|
| |||
Installation Clearances |
|
| |||
| Roof Terminal |
| Clearances to Combustibles | ||
Air |
|
|
|
|
|
Intake |
|
| 15 cm |
| 15 cm |
|
|
|
| ||
|
| Flue | 3 m | 50 cm | 50 cm** |
Wall |
|
|
| ||
| 60 cm |
|
|
| |
Terminal |
|
|
| ||
|
|
|
| ||
|
|
|
|
| 30 cm |
|
|
| 2.5 - 3.5 m* |
|
|
|
|
|
| **80 cm is necessary to service heater. | |
*Heaters may be mounted at a higher level if destratification |
|
| |||
fans and/or turn down nozzles are installed. |
|
| |||
Fax: +44(0)121 506 7701 | Telephone: 716.852.4400 | ||||
Unit A, Kings Hill Business Park | Service Telephone: +44(0)121 506 7709 | 1250 William Street | Fax: 716.852.0854 | ||
Darlaston Road, Wednesbury | Service Fax: +44(0)121 506 7702 | P.O. Box 44 | Toll Free: 800.828.7450 | ||
West Midlands WS10 7SH UK | Buffalo, NY |
| |||
Telephone: +44(0)121 506 7700 |
| ||||
|
|
Installation Code and Annual Inspections:
All installations and service of ROBERTS GORDON® equipment must be performed by a contractor qualified in the installation and service of equipment sold and supplied by
For installations at elevations above 2000' (610 m), the appliance shall be derated 4% for each 1000' (305 m) of elevation above sea level.
Further Information:Applications, engineering and detailed guidance on systems design, installation and equipment performance is available through ROBERTS GORDON® representatives. Please contact us for any further information you may require, including the Installation, Commissioning, Operation and Service Manual.
These products are not for residential use.
© 2007 | Printed in U.S.A. | P/N 91040028 Rev B |