Roberts Gorden CTU 22 TO 115 Fire Hazard, close to heater, injury or property damage

Models: CTU 22 TO 115

1 51
Download 51 pages 26.29 Kb
Page 51
Image 51
close to heater.

SECTION 16: REMOVAL AND REPLACEMENT PARTS

Attach this information to the wall near the ROBERTS GORDON® heater

®

Read the Installation, Commissioning, Operation and Service Manual thoroughly before installation, operation or service.

OPERATING INSTRUCTIONS

WARNING

 

 

 

1.STOP! Read all safety instructions on this information sheet.

2.Open the manual gas valve in the heater supply line.

3.Turn on electric power to the heater.

4.Set the thermostat to desired setting (above ambient temperature). The automatic starting sequence begins.

NOTE: Following long shutdown periods, the burner control may go to to 'LOCKOUT' during the start sequence. Push the reset button to recommence firing. Contact service department if 'LOCKOUT' continues (see manual for details).

TO TURN OFF THE HEATER

1. Turn the thermostat/time switch to 'OFF'. The burner will turn 'OFF'

 

Fire Hazard

immediately, but fans will continue to cool heat exchanger until the fan

 

 

thermostat switches off.

 

Some objects can catch fire or explode when placed

 

 

 

 

IF THE HEATER WILL NOT OPERATE, TO ENSURE YOUR SAFETY,

close to heater.

 

 

 

FOLLOW THESE INSTRUCTIONS TO SHUT DOWN YOUR HEATER

Keep all flammable objects, liquids and vapors the

 

 

 

 

1. Set the thermostat to off or the lowest setting.

required clearances to combustibles away from heater.

 

 

2. Turn off electric power to the heater.

Failure to follow these instructions can result in death,

3. Turn off the manual gas valve in the heater supply line.

4. Call your registered installer/contractor qualified in the installation

injury or property damage.

and service of gas-fired heating equipment.

 

 

Installation Clearances

 

 

 

Roof Terminal

 

Clearances to Combustibles

Air

 

 

 

 

 

Intake

 

 

15 cm

 

15 cm

 

 

 

 

 

 

Flue

3 m

50 cm

50 cm**

Wall

 

 

 

 

60 cm

 

 

 

Terminal

 

 

 

 

 

 

 

 

 

 

 

 

30 cm

 

 

 

2.5 - 3.5 m*

 

 

 

 

 

 

**80 cm is necessary to service heater.

*Heaters may be mounted at a higher level if destratification

 

 

fans and/or turn down nozzles are installed.

 

 

Roberts-Gordon Europe Limited

Fax: +44(0)121 506 7701

Roberts-Gordon, LLC

Telephone: 716.852.4400

Unit A, Kings Hill Business Park

Service Telephone: +44(0)121 506 7709

1250 William Street

Fax: 716.852.0854

Darlaston Road, Wednesbury

Service Fax: +44(0)121 506 7702

P.O. Box 44

Toll Free: 800.828.7450

West Midlands WS10 7SH UK

E-mail: uksales@rg-inc.com

Buffalo, NY 14240-0044 USA

 

Telephone: +44(0)121 506 7700

E-mail: export@rg-inc.com

 

 

 

Installation Code and Annual Inspections:

All installations and service of ROBERTS GORDON® equipment must be performed by a contractor qualified in the installation and service of equipment sold and supplied by Roberts-Gordon and conform to all requirements set forth in the ROBERTS GORDON® manuals and all applicable governmental authorities pertaining to the installation, service and operation of the equipment. To help facilitate optimum performance and safety, Roberts-Gordon recommends that a qualified contractor annually inspect your ROBERTS GORDON® equipment and perform service where necessary, using only replacement parts sold and supplied by Roberts-Gordon.

For installations at elevations above 2000' (610 m), the appliance shall be derated 4% for each 1000' (305 m) of elevation above sea level.

Further Information:Applications, engineering and detailed guidance on systems design, installation and equipment performance is available through ROBERTS GORDON® representatives. Please contact us for any further information you may require, including the Installation, Commissioning, Operation and Service Manual.

These products are not for residential use.

© 2007 Roberts-Gordon, LLC

www.rg-inc.com

Printed in U.S.A.

P/N 91040028 Rev B

45

Page 51
Image 51
Roberts Gorden CTU 22 TO 115 service manual Fire Hazard, close to heater, injury or property damage