SECTION 15: TROUBLESHOOTING

15.2 Troubleshooting For Automatic Ignition Burner Systems

 

 

There are two burner controls used: Honeywell S4563C and

 

 

 

 

 

 

WARNING

 

S4565C. They both have similar operating sequences. To

 

 

measure flame current, connect a 0 - 50 μA DC meter in

 

 

 

 

 

 

 

 

series with the flame probe. If the meter reads negative

 

 

values, then reverse the test leads.

 

 

 

 

 

Electrical Shock Hazard

Start

 

 

Do not touch ignition components.

 

 

 

Are gas & electrical

 

 

Voltage from ignition components is high.

No

Turn on supplies.

 

supplies on?

Failure to follow these instructions can

 

 

 

 

 

result in death or electrical shock.

Yes

 

 

 

 

 

 

 

 

Has the thermostat limit

 

 

 

 

Is the green light on?

No

Are external controls on?

Yes

thermodisc operated or light

faulty? Reset or replace as

 

 

 

 

 

 

 

 

necessary.

Yes

 

 

 

 

 

 

 

Press in lockout reset button

 

 

 

Is red lockout light on?

Yes

on rear of heater or remote

 

 

 

 

 

reset button if fitted.

 

 

 

No

 

 

 

 

 

Does flue fan run?

No

 

Yes

 

Does air pressure switch

No

change over?

 

Yes

Wait 30 - 40 seconds.

Is ignition spark operating? No

Yes

 

Does the flame light?

No

Yes

 

Is red lockout light on?

Yes

Is 230 V supply at fan

Yes

connections?

 

No

Burner control faulty or plug in connections faulty. Repair or replace as necessary

Check for too much flue/air inlet

duct. Check for blockage in

combustion air circuit.

Check for faulty air pressure

switch. See section 16.5.

Is HT lead okay and

connected? Yes Is spark electrode okay?

Is the gas valve operating?

To test valve, No see Section 15.4.

Is the flame current at

least 1 µAmp DC when No the flame lights?

Flue fan faulty replace

Ignition control faulty replace.

See Section 15.6.

Replace valve.

Trace fault in supervision system. See Section 16.3.

No

Heater Operating

TROUBLESHOOT ENDS. No

If problems persist, contact

For your safety and optimum heater performance,

use only ROBERTS GORDON® replacement parts.

ROBERTS GORDON® at

Conduct Commissioning procedure as shown

Tel: +44(0) 121 506 7709

www.rg-inc.com

on Page 24, Section 11.

33

Page 39
Image 39
Roberts Gorden CTU 22 TO 115 For your safety and optimum heater performance, Conduct Commissioning procedure as shown