16.5 Pressure Switch

SECTION 16: REMOVAL AND REPLACEMENT PARTS

16.5 Pressure Switch

Pull off 3 way connector. Spring open plastic clips of mounting cradle. Replace with correct type of pressure switch for model. The pressure switches are colour coded for each pressure setting.

Manual background WARNING

Carbon Monoxide Hazard

Use correct pressure switch specified for each model.

Use of incorrect pressure switch could cause unsafe condition.

Failure to follow these instructions can result in death or serious injury.

Carry out a commission after working on or changing a pressure switch. See Page 24, Section 11.

Pressure

CTU-22

CTU-30

CTU-35

CTU-40

CTU-50

CTU-60

CTU-75

CTU-90

CTU-100

CTU-115

Switch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RG P/N

90439801

90439810

90439804

90439803

90439810

90439802

90439811

90439807

90439811

90439807

 

 

 

 

 

 

 

 

 

 

 

Colour

pink

grey

white

grey

grey

yellow

grey

brown

grey

brown

Code

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set Point

0.57

0.92

1.17

1.02

0.87

0.80

1.79

1.69

1.79

1.69

mbar

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

in wc

0.23

0.37

0.47

0.41

0.35

0.32

0.72

0.68

0.72

0.68

 

 

 

 

 

 

 

 

 

 

 