Operation

Control Panel

Tenperture control set

Timer set control

Oscillation mode Fan speed control

LCD display

Power control

Sleep mode

Mode control

Power Control

The power control button turns the unit on and off. When you press the button, the unit begins to operate.

Mode Control

The Mode Control has 3 settings (four settings on 4012H).

Auto Cool

Dehumidify Fan / Heat

Cool Mode

Press the Mode Control button to select Cool mode. The green light will show on the display.

The unit displays “present room temperature.” The temperature range settings are between 64~88 °F

A. In Cool mode, use the or button to adjust and set the desired temperature for the room. After 3 seconds the display will return back to the present room temperature. Note: The air exchange hoses must be vented through window kit when in this mode.

Dry (Dehumidify) Mode

Press the Mode Control button to select Dry (dehumidify) mode. The light will show on the display.

When the Dehumidify mode is on, the temperature buttons do not function. The fan speed can be adjusted only if the temperature in the room is higher then 77 ° F. If it is below this temperature, the fan speed is automatically fixed to “low” and cannot be adjusted. When the humidity in the room is 50% or lower, the compressor will not run and the unit will not dehumidify.

NOTE: The exhaust hose must be connected to remove the humidity.

Fan Mode

Press the Mode Control button to select Fan mode. The light will show on the display. The air is circulated throughout the room with no cooling.

Heat Mode (only ARP-4012H)

Press the Mode Control button to select Heat mode. The red light will show on the display.

The unit displays “present room temperature”. Heating is only activated when the temperature in the room is below 81° F. The temperature setting can be adjusted between 64 and 81° F. B. In Heat mode, use the or button to adjust and set the desired temperature for the room. After 3 seconds the display will return back to the current room temperature.

Note: The two air exchange hoses must be vented through window kit when in this mode.

8

Page 8
Image 8
Royal Sovereign ARP-4010, ARP-4009, ARP-4012H owner manual Operation